Tendering Authority: Military Engineer Services
Tender ID3510968
Organisation NameMilitary Engineer Services
Tender BriefCorrigendum : Spl Repair/ Replacement Of Ceiling Fans And Provn Of Geysers, Water Cooler, Desert Cooler, Ac, Security Light, Wall Fan And Other Sanctioned Works Under Age E/m At Nams
Last Date For Submission26th Mar, 2026
Opening Date30 Mar, 2026
Cost
Document Cost500.00
EMD98280.00
Estimated Cost4914000.00
Location
CityAmritsar
StatePunjab

Register to see full details

BOQ Items
#ItemQtyUnits
1S & F in repairs, installation, commissioning and 1Phase Street Light Timer Switch shall be ASTA CPRI OEM made out of Polycarbonate with glass fiber reinforced and size should be not less than 225 x 295 x 122 mm . The Polycarbonate shall be environment friendly, recyclable, halogen & silicon free, anti acid & anti corrosive. The Junction Box shall be rated for Degree of ingress Protection IP 66/67/69 in accordance with IEC 60529.Weatherproof UV-resistant, rainwater-proof, temperature-resistant. The gasket material of JB shall be Polyurethane and the gasket shall be internally embedded. The Street Light Timer Switch Box shall be complies with requirements of the standards IEC 60998 - 1, IEC 60670 - 22 & IEC 60670 - 2 - 5. The JB Colour according to RAL 9011. The manufacturer of Street Light Timer Switch Enclosure shall submit a copy of IEC Certificate . For better safety the Polycarbonate enclosure and shall be fire retardant & self - extinguishing in accordance with IEC 60695 - 2 - 11, DIN VDE 0304 Part - 3, UL Subject 94 for Flammability V-2. It should be tested at Glow Wire test for 960 degree Centigrade & Current Carrying Capacity upto 102Amps. The impact strength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechanical load shall be in accordance with EN 50298 - 98 for IK 08 including Two Nos. 4 pole connector (Incomer & Outgoing )and one no. MCB DP 'C' curved 25 A with Digital Street Light Timer, Suitable Contractor as per MCB, Also Privided Cable Glands for all cables and chromium plated clamps and nut bolts complete all as per manufacturer s instructions. Make : Cat Part :- Hensel/Siemens/GE Power/Rittal. Manufacturer should submit routine test certificate of CJB/PJB 1.00Each
2S & F in repairs, installation, commissioning and testing Supply of LT Cable junction box outdoor shall be made out of Polycarbonate with glass fiber reinforced and size should be not less than 155 x 210 x 92 mm(upto Cable Size 16sq.mm). The Polycarbonate Junction Box shall be environment friendly, recyclable, halogen & silicon free, anti acid & anti corrosive. The Junction Box shall be rated for Degree of ingress Protection IP 66/67/69 in accordance with IEC 60529.Weatherproof, UV-resistant, rainwater-proof, temperature-resistant. The gasket material of junction box shall be Polyurethane and the gasket shall be internally embedded. The Junction Box shall be complies with requirements of the standards IEC 60998 - 1, IEC 60670 - 22 & IEC 60670 - 2 - 5. The Junction Box with Suitable Connectors or Terminal Trip. The manufacturer of Junction Box / Enclosure shall submit a copy of IEC Certificate.The JB Colour according to RAL 9011. The Junction Box supply as per approved make List in MES Junction Box category. For better safety the Polycarbonate enclosure and shall be fire retardant & self - extinguishing in accordance with IEC 60695 - 2 - 11, DIN VDE 0304 Part - 3, UL Subject 94 for Flammability V-2. It should be tested at Glow Wire test for 960 degree Centigrade & Current Carrying Capacity upto 102Amps. Junction Box with One No MCB 6Amp SP 10KA C-Curve for Manual operate to LED Light . The impact strength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechanical load shall be in accordance with EN 50298 - 98 for IK 08 including Four Pole. connector for Cable Loop, 3 Nos PVC IP68 Suitable Glands as per Cable and Junction Box with Pole mounting clamps and nut bolts complete all as per manufacturer s instructions. Note: Manufacturer should submit routine test certificate of CJB/PJB as per above.8.00Each
3Supply & fixing LED street light 90 W 230 volts with surge protection not less than 4 KV inbuilt in driver & minimum 10 KV separate in the light housing. Powder coated pressure die cast aluminium housing , IP-65/66 protection, high power LED street light with the heat resistant thoughened glass lens and making electrical connections pvc insulated sheathed 3 core 1.5 sqmm copper conductor from street light to junction box complete all as specified and directed. Notes: Driver shall be potted antivibration type. LM-79 and LM-80 for 50000 burning hours. CRI(colour Rendring Index) of fixture shall be 70. CCT (colour correlated Temp) of fixture shall be 5700K 300K. System Lumen Efficiency shall be>100 Lm/W. 10 KV separate Surge protection shall be provided as a part of fitting. PCB used shall be MC PCB type. The fitting shall have arrangement so that maintenance required, if any can be carried out from Top cover.8.00Each
4Supply and installation of dip galvanised octagonal poles 9 m long top dia (A/F) 70 mm bottom dia (A/F) -minimum 130 mm having thickness 3 mm base plate 200 mm x 200 m x 16 mm(LxBxT) including bolt size 4 x 20 mm (Nox dia) , 200 mm pitch circle dia 600 mm bolt length , 100 mm projected bolt length having door opening of sizes 90 x 500 mm above GL and having hot dip galvanized singlr arm plane arm bracket 1000 mm long for pole having top 70 mm A/F for mounting street light fitting fixed on top with nut bolts washers including provision of cable connector for three phases supply and one No MCB SP of 0.5 A to 6A complete alongwith necessary iron work complete all as per manufacturer s instructions. NOTE :- Excavation, earth work, necessary iron work, PCC and RCC work is included in quoted rate.8.00Each
5Supply and Laying in trenches or passing through pipe or fixing to pole/wall UG cable XLPE, of cross section area 25 sqmm 4 core, PVC insulated, armoured heavy duty electric cable with aluminum conductor, 1100 Volts grade complete all as specified and directed. Note : Earth work/ sand cushioning shall be measured and paid separately.280.00RM