Complete Tender Details

Empowering Indian businesses in the procurement ecosystem since 2012

Tendering Authority: Indian Institute Of Technology
Tender ID3673306
Organisation NameIndian Institute Of Technology
Tender BriefCorrigendum : Supply, Installation, Testing and Commissioning Of 2500 Cfm Ahu Including Mixing Chamber And Hepa Filter Chw Piping And Associated Works At Aces 122-123 Clean Lab
Last Date For Submission30th Mar, 2026
Opening Date31 Mar, 2026
Cost
Document Cost0.00
EMD11458.00
Estimated Cost572875.00
Location
CityKanpur
StateUttar Pradesh

Register to see full details

BOQ Items
#ItemQtyUnits
1SITC of double skin sheet metal construction Vertical/horrizontal type floor mounted Single/Double Decker air handling units (AHU) with mixing chamber of panels consisting of pre plasticized/coated G.I. casing of thickness 0.6 mm outside layer and 0.6 mm inside layer with with 25 mm thick injected PUF of density not less than 40 Kg/CuM and i/c 25 mm thick Open cell nitrile acoustic insulation injected between intermediate & inner skin with 0.6 mm perforated Al./GI inner sheet. All frame work shall be thermal break with extruded aluminium profile with Thermal Barrier. The air handling units shall be complete with Supply,Return & Fresh air low leakage manual Aluminium dampers, Filter-sections with Pre filter 50 mm thick (EU-4) box type, Fine filter with 305 mm thick (EU-7) flange type & 305 mm thick (EU-13) flange type HEPA filter. coil section with 6 Rows Deep chilled water AHRI certified 12.7 mm dia Cooling cooper coil of min 0.41 mm thick with Copper Header & 0.15 mm aluminium fins construction with GI/SS Casing , fan section complete with backward curved DIDW centrifugal fan , V-belts, drive package, VFD compatible variable speed squirrel cage induction TEFC IE-3 motor, Motor shall be suitable for 415 10% volts, 50 Hz, 3 phase AC supply. having limit Switch, LED light ,fire retardent flexible connection, 20 G SS-304 stainless steel drain pan having 13 mm nitrile insulation and V.I. pads all complete as per specifications.AHUs shall be selected for a maximum face velocity of 500 FPM (2.5 MPS), Fan outlet velocity shall not exceed 1800 FPM(9.15 m/s).
22500 CFM, 6 Rows, 135 mm WG static pressure1No
3Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled/condenser water piping plumbing i/c fabrication of bends / elbows, tees, reducers etc) inside the building (with necessary clamps, wooden/puff support, vibration isolators, primer/ enamel paint, fittings but excluding valves, strainers, gauges etc.) as per specifications and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. C class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes up to 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
440 mm10Mtr
5Supplying, fixing, testing and commissioning of following BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & Oring PN 16 pressure rating size 200 mm to 400 mm gear type with removable wheel and below 200 mm with hand lever operated for chilled water/hot water circulation in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications as specified.
30th Mar, 2026

6 Days Left