| 1 | Supply installation, commissioning and testin of silent type, diesel engine driven factory assembled floor assembled floor mounted, generating set of capacity 100 KVA, 3 Phase, 4 wire, 50 Hz , 1500 RPM completed including AMF Panel suitable for 100 KVA DG Set as per CPCB IV norms, safety control and metering equipments installed with common base platform with floor mounted wall (Mounted/in built fuel tank) of suitable capacity and including all excavation PCC foundation anti vibration pads/dampers as directed by (OEM) manufacture Foundation Designand other accessories comprising of following :-
(i) Fly wheel to suit flexible coupling.
(ii) Flexible coupling with guards
(iii) Air cleaner with filters
(iv) lubricating oil filter, fuel filter, fuel pre filter
(v) Anti-vibration pads as recommeded by manufacturer
(vi) Fuel injecting system with injection pump, nozzles, electronic governor of suitable capacity
(vii) Electric start equipment
(viii) Alternator for charging battery -01 No alongwith cutout make-Lucas/ equivalent as approved by GE
(ix) Lead acid storage battery 12 volts as recommended by manufacturer's Make EXIDE/AMRON/LUMINIOUS along with copper battery lead and connector
(x) Battery rack made out of MS angle iron 40mmx40mmx5mm & 150 mm height
(xi) Standard safety device
| 2.00 | Each |
| 2 | (xii) Daily service fuel tank of suitable capacity but not less than 200 ltrs with level indicator inlet , strainer fuel outlet, drain plug and air vent and locking arrangement etc. including fuel pipe connectons conealed type with GI pipe medium grade from fuel tank of the DG set and over flow from the DG set to fuel tank complete with gate valve.
(xiii) Exhaust silencer (Residential silencer) with exhaust piping of suitable size brought out side canopy and complete length of silance and exhaust piping continuously wrapped with 12mm dia asbestos rope.
(xiv) Engine control panel as per manufacturer instructions duly wired and comprising of the following :-
(aa) Lubrication oil temperature guage-1 No
(ab) lubrication oil pressure gyage-1No
(cc) water temperature guage-01No
(dd) Starting switch with Kay-01 No
(ee) Battery charging ammeter, batter charging lamp, and fuse box, voltmenter, engine speedometer, engine running hours meter, frequency meter , KWH meter etc
(ff) indicator lamp etc.
(B) ALternator : 100 KVA at 0.8 power factor , self regulated , self exited, screen protected 3 phase with neutral 415 volts 50 Hz 15oo RPM as per IS 2613/IS-4722 complete with automatic voltage regulator including making cable connections, insulation class -F and alternator control panel with MCCB , AMp Meter with CTs, Volt meter, Frequency meterm indicator R,Y, B & selecter switches etc as supplied by maufacturers.
(C) Base Frame : Strurt , MS fabricated , channel iron base frame for mounting the Engine & alternator
| | |
| 3 | (D) ACOUSTIC ENCLOSURE: Acoustic enclousure weather proof of suitable size to accommodate DG set of 100 KVA , modular contruction , fabricated out of 3 mm thick , cold annealed CRC sheet duly epoxy painted. Doors to be provided with high quality EDPN gasket , duly epoxy painted. the canopy to be equipped with heavy duty fans of reputed manyfacturer for air circulation. Rock wool to be used for insulation.
(E) Repair tools to be supplied as under:-
(i) Ring spanner set of 10-01 set.
(ii) Screw driver 6"x8" and 12"x14" -1No each
(iii) adjustable spanner 12" -1 No
(iv) Double end spanner set of 10-01No
(v) Cutting pliers10" 1No
(vi) Techo meter -1No
(vii) Tool kit box-01No
(G) Maint spares to be supplied as under:-
(i) All type of filters -02 each
(ii) V-belt -01 sert
(iii) carbon brushes - 01 set
Note: the enginer of DG set suitably be de-rated to suit the climatic condition of Haldwani area, so as to give desired outputs including 10% overload. | | |
| 4 | Supply , laying , connecting, testing and commissioning of 185Sqmm 3.5 core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable with stranded aluminium conductor 1100 Volts laid in trenches, fixed to walls/ drawn through pipe and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed.
Note;-(Excavation, earthwork send cushioning and cable protection shall be measured and paid for separately.) | 235.00 | RM |
| 5 | Supply , laying , connecting, testing and commissioning of 95 Sqmm 3.5 core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable with stranded aluminium conductor 1100 Volts laid in trenches, fixed to walls/ drawn through pipe and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed.
Note;-(Excavation, earthwork send cushioning and cable protection shall be measured and paid for separately.) | 40.00 | RM |