Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 3492960 |
|---|---|
| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Repair/maintenance Of 11 Kv Vcb Ht Panels Including Replacement Of Spares With Other Allied Works At New Dockyard Substations At Naval Dockyard Visakhapatnam Under Ge (i) (dm) Visakhapatnam |
| Last Date For Submission | 25th Mar, 2026 |
| Opening Date | 27 Mar, 2026 |
| Document Cost | 500.00 |
|---|---|
| EMD | 99520.00 |
| Estimated Cost | 4976000.00 |
| City | Visakhapatnam |
|---|---|
| State | Andhra Pradesh |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Taking down HT Switch gear vaccum circuit breaker of capacity 630 Amps to 1200 Amps, 12kv/11KV, Schneider make HWX Model for carrying out following repairs, overhaluing, servicing, preventive maintenance and reflixing the same after carrying out repairs / overhauling complete all as specified and as directed. (a) Tripping off the breaker, rackout the breaker complete from the panel along with trolly for servicing / inspection/ overhauling. (b) Servicing / inspecting/ checking automatic safety shutter operation for service ability and replacement of spares if required. (c ) Servicing /inspecting / checking of busbar spout and circuit spout connections for RYB Phases and replacement of spares if required. (d) checking of breaker ma9in mechanism assembly, fixed contacts and cuurrent carrying parts of the breaker, trolley, insulated asembly etc. (e) setting, reassembling, cleaning adjustment of fixed contacts main contact, acring contact and moving contact for proper setting of auxiliary contacts operatingg mechanism. | 40.00 | Each Job |
| 2 | (f) Servicing / inspecting / checking of secondary socketd / busbar earthing plugs / earthing sockets and replacement of spares if required. (g) checking, setting and adjustment of rackin and rackout operation of the breakedr trolley. (h) Decarbonising of busbar and connected items. (j) Lubrication and greasing of all moving parts of the trolley, stopper bolt for proper operating. Note : (i) The rate quoted shall be deemed to be include for necessary T & P, Nuts, bolts, washers, gasket, insulation tape, HT Sleeve, monoplast compound to put in to the VCBs and paneles in serviceable condition, testing and commissioning (ii) Replacement of defective parts of the VCB Shall be measured and paid separately. | ||
| 3 | Supply and fix including dismanting taking out unservicebable buffer (for opening spring ) for 800 A to 1600A schneider make 11 KV VCB all as specified and directed. Make :- Schneider only, Part No - MVIJ00098-01 | 15.00 | Each |
| 4 | Supply and fix including dismanting taking out unservicebable buffer (for closing spring ) for 800 A to 1600A schneider make 11 KV VCB all as specified and directed. Make :- Schneider only, Part No - MVIJ00056-01 | 15.00 | Each |
| 5 | Supply and fix including dismantling taking out unserviceable breaker wheel - cast iron, for 800A to 2500A Scheider make 11 KV VCB all as specified and directed. Make :- Schneider only. Part No - MVIJ00025-01 | 2.00 | Set of 04 |
6 Days Left