Tender ID4620732
Organisation NameMilitary Engineer Services
Tender BriefCorrigendum : Repair / Replacement Of Earthing Infrastructure Including Lightening Protection System At Air Force Station Adampur
Last Date For Submission14th Jul, 2026
Opening Date16 Jul, 2026
Cost
Document Cost500.00
EMD80000.00
Estimated Cost4000000.00
Location
CityAdampur
StatePunjab

Register to see full details

BOQ Items
#ItemQtyUnits
1M&L for providing earthing with and including GI earth plate electrode 6 mm thick of size 600 mm x 600 mm with 4 mm dia GI wire earthing lead complete all as shown in electrical plate No. 3 and as per MES SSR Part-I specificatons including dismantling old, complete all as specified and directed. 10Each Set
2NOTES APPLICABLE TO SERIAL ITEM 1: (a) The unit rate includes earthing lead and protection pipe upto 7.5 metre from top of earth plate. (b) Factory made PCC pit with cover shall be fixed at least 500mm away from the earth pit. (c) Earth resistance should be less than five Ohm. In case the test results are not found below five Ohm, complete earthing shall be redone by contractor without any extra cost to Govt .
3M&L for providing earthing with and including GI earth plate electrode 6 mm thick of size 600 mm x 600 mm with 25 mm x 4 mm GI strip earthing lead complete all as shown in electrical plate No. 3 and as specified in SSR Part-I specifications including dismantling old, complete all as specified and directed. 60Each Set
4M&L for providing earthing with and including GI earth plate electrode 6 mm thick of size 600 mm x 600 mm with 32 mm x 6 mm GI strip earthing lead complete all as shown in electrical plate No. 3 and as specified in SSR Part-I specifications including dismantling old, complete all as specified and directed. 10Each Set
5NOTES APPLICABLE TO SERIAL ITEM 2 & 3: (a) The unit rate includes earthing lead and protection pipe upto 7.5 metre from top of earth plate. (b) Factory made PCC pit with cover shall be fixed at least 500mm away from the earth pit. (c) Earth resistance should be less than ten Ohm. In case the test results are not found below ten Ohm, complete earthing shall be redone by contractor without any extra cost to Govt .