Complete Tender Details

Empowering Indian businesses in the procurement ecosystem since 2012

Tendering Authority: Military Engineer Services
Tender ID4406572
Organisation NameMilitary Engineer Services
Tender BriefCorrigendum : Repair/maint Of External Water Supply Network At Akhnoor Mil Stn Under Ge (n) Akhnoor
Last Date For Submission22nd Jun, 2026
Opening Date29 Jun, 2026
Cost
Document Cost500.00
EMD98000.00
Estimated Cost4900000.00
Location
CityAkhnoor
StateJammu and Kashmir

Register to see full details

BOQ Items
#ItemQtyUnits
1Excavation in trenches n. exc.1.5m wide and n. exc. 1.5m in depth for foundation of pole, laying of pipe line and getting out in any type of soil complete all as specified and directed.314.55Cum
2Returning filling in including spreading ,levelling,watering and wall ramming in layers not exc 25cm in any type of soil complete all as specified and directed.278.10Cum
3Removal of excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed.36.46Cum
4Design, fabrication, installation, testing and commissioning of 400 ampere auto starter cum fault analyzer cum protection & control panel at Stage-2 including following job:- 1) Fabrication of Power Handling Unit (PHU) / Auto Starter with power contactor MNX-400-2Nos., MNX-185-1No. of L&T make along with MCCB of 630 ampere rating also of L&T make. 2) The system should be provided with a solid state fault analyzer cum controller. 3) The complete system should be enclosed in a floor / wall mounted MS sheet enclosure / box of suitable gauge and dimensions with proper entry and exit holes for incoming and outgoing cables. The enclosure should be finished with powder coated painting from inside as well as from outer surface of approved colour. Job also includes mounting of the panel to the wall / floor of the pump room. METERING: 4) The enclosure should be front shutter mounted with key locking system having glass window. Digital electronic voltmeter & ampere meter should be provided along with the required current transformer and selector switches. The internal control wiring should be done with flexible PVC LT cable with proper thimbling at each end. FEATURES AND SPECIFICATIONS: 5) The system should trip the motor on power failure and on appearance of an electrical fault mentioned below which may otherwise damage the motor field coils and should not restart automatically until unless the system is reset manually, thus providing automation to the system and protection to the motor. 1.00Each
5Item No 4 Contd 6) The system shall provide protection against: - a. Low voltage below 350 V b. High Voltage above 450 V c. Single phasing d. Reverse phasing e. Un Balanced phasing f. Dry running g. Overloading INFORMATION SECTION: - In addition the system should have the following audio & visual features for a quick and accurate diagnosis of the appeared fault / status for a speedy rectification of the system. 7) Separate LED fault / status indicators. 8) LED phase indicators. 9) An isolation by pass system, for fault analysis system, with a blinking indicator. 10) 3 LED, contactor COIL OK , indicators, one for each of the contactors / coils. LED star & delta indicators to access the star to delta timing. 11) A tamper proof starting system to avoid manipulations by the motor operator to keep the system in a permanently ON position. Job further includes providing & fitting of accessories for connection from main panel. Complete job includes cost of panel/ material, labour charges, transportation/ shifting charges up to site of work, including installation, testing, commissioning and all taxes.
22nd Jun, 2026

6 Days Left

WhatsApp