| 1 | Dismantling & Taking down existing panel & Supply, installation, fabrication, testing and commissioning of new LT Panel board, (CPRI approved) Factory made cubical type, Outdoor type, floor mounted, factory made out of 50mm x 50mmx5mm angle iron frame and 3.15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 800 amps (03 Nos 800 Amps for Phase and 01 No 400 Amps for neutral) rated aluminium bus bar complete powder coated paint with and providing necessary foundation/plateform of the feeder pillar and provision for incoming and outgoing cable, cable gland, replacement of lugs for existing cables as per site requirement and proper finshing as per existing surface complete all as specified and directed by Engr- in- Charge. Note : (i) The quoted rate shall be of all inclusive.(ii) Drawing for LT feeder piller box shall be got approved by GE before fabrication.(iii) Platform for the feeder pillar board with PCC 1:2:4 15 Cm thick in foundation, Brick (Sub Class B) work in CM 1:6 ,rendering 1:6 on exposed surfaces and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting legs of panel . The platform shall be of 40 cm below ground level and 60Cm height above ground level . Rate for Platform shall be included in the quoted rate.
(a) Incoming
(i) MCCB 04 Pole 36 kA, 500 Amp,415 Volts, fixed thermal & magnetic release (Qty 01 No).
(b) Out goings
(i) MCCB 04 Pole 25 KA, 250 Amp, 415 Volts, fixed thermal & magnetic release (Qty - 02 Nos)
(ii) MCCB 04 Pole 25 KA, 160 Amp, 415 Volts, fixed thermal & magnetic release (Qty - 02 Nos)
(iii) Aluminium bus bar suitable size 3 phase, 4 wire 800 Amp,415 V, duly insulated - set of 4
(iv) Digital Volt meter 0-500V with slector switch.
(v) Digital Amp meter 0-500 amp with CT 500/5A and selector switch.
(vi) Indicating lamp (RYB)LED Type - set of 3 (Note: All MCCB rating Ics/Icu = 100% .) | 2.00 | Each Job |
| 2 | Dismantling & Taking down existing panel & Supply, installation, fabrication, testing and commissioning of new LT Panel board, (CPRI approved) Factory made cubical type, Outdoor type, floor mounted, factory made out of 50mm x 50mmx5mm angle iron frame and 3.15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 600 amps (03 Nos 600 Amps for Phase and 01 No 300 Amps for neutral) rated aluminium bus bar complete powder coated paint with and providing necessary foundation/plateform of the feeder pillar and provision for incoming and outgoing cable, cable gland, replacement of lugs for existing cables as per site requirement and proper finshing as per existing surface complete all as specified and directed by Engr- in- Charge. Note : (i) The quoted rate shall be of all inclusive.(ii) Drawing for LT feeder piller box shall be got approved by GE before fabrication.(iii) Platform for the feeder pillar board with PCC 1:2:4 15 Cm thick in foundation, Brick (Sub Class B) work in CM 1:6 ,rendering 1:6 on exposed surfaces and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting legs of panel . The platform shall be of 40 cm below ground level and 60Cm height above ground level . Rate for Platform shall be included in the quoted rate.
(a) Incoming
(i) MCCB 04 Pole 36 kA, 500 Amp,415 Volts, fixed thermal & magnetic release (Qty 01 No).
(b) Out goings
(i) MCCB 04 Pole 36 KA, 315/320 Amp, 415 Volts, fixed thermal & magnetic release (Qty - 01 Nos)
(ii) MCCB 04 Pole 25 KA, 250 Amp, 415 Volts, fixed thermal & magnetic release (Qty - 01 Nos)
(iii) MCCB 04 Pole 25 KA, 200 Amp, 415 Volts, fixed thermal & magnetic release (Qty - 01 Nos)
(iv) MCCB 04 Pole 16 KA, 160 Amp, 415 Volts, fixed thermal & magnetic release (Qty - 01 Nos)
(v) Aluminium bus bar suitable size 3 phase, 4 wire 800 Amp,415 V, duly insulated - set of 4
(vi) Digital Volt meter 0-500V with slector switch.
(vii) Digital Amp meter 0-500 amp with CT 500/5A and selector switch.
(viii) Indicating lamp (RYB)LED Type - set of 3 (Note: All MCCB rating Ics/Icu = 100% .) | 1.00 | Each Job |
| 3 | M&L for in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured heavy duty electric power cable 1100 volts with stranded aluminium conductor of size 300 Sqmm 3.5 core laid in trenches or under road complete all as specified and as directed. (Note: Excavation, cable protection work will be measure & paid separately) | 320.00 | RM |
| 4 | All as per serial item No 3.00 here-in- before but of size 185 Sqmm 3.5 core complete all as specified and as directed. | 500.00 | RM |
| 5 | All as per serial item No 3.00 here-in- before but of size 120 Sqmm 3.5 core complete all as specified and as directed. | 380.00 | RM |