| 1 | Supply and fixing in replacement of Lithium base Energy efficient integrated Solar street light of 40watt in Aluminium Die casting body / FRP Bpdy , corrosion resistance,integrated PV panel Automatic dusk to input voltage 12.8V with suitable battery ,Driver efficiency .85%,PV module itself will be used to sense the ambient light to switch ON/OFF the Lamp, inbuilt MPPT charge controller, IP65,both PIR and fixed dimming available,4500 lumens (at full brightness) with grater than 150 lumen per watt,5700ANSI, cool white(5500K-6500K),CRI.70,moptical used, Metal core PCB,Low voltage cutoff ,high power LED,wide beam Angle(120 degree) LED Life 50000 hrs, weight less than 15 kg with GReen/Red indicator switch with suitable battery rating 12.8V-BIS standard complete all as specified.
Make: Orient/Havells/Crompton Protections: Short circuit, overload,Reserve polarity and battery protection.Firm should provide vital parametres Test report from NABL accredited lab and should be of made in India with CE & ROHS complaint.
| 25.00 | Each
Set |
| 2 | S & F street light GI bracket of 1.2 mtr long for building security / pole mount light made out of 40mm dia medium grade GI pipe bend to shape of 120 degree end welded at required including 02 Nos MS clamp of FL 40 x 6mm including nuts bolts & washers complete necessary fixing arrangements on pole and including Dismantling old U/S GI bracket of any size complete all as specified. | 25.00 | Each |
| 3 | Supply, installations, testing and commissioning factory made out door cubical type LT panel board dust and vermin proof , free standing, floor mounting type mounted on and incluidng 1:3:6 PCC foundation as requried at site and of fabricated by 3.15 mm thick CRCA sheet over MS 40 X 40 X 5 mm thick angle iron frame of requried type for support with double door both sides open type with necessary locking arrangement with slopped roof on top duly painted with two coats of powder coated semense gray paint complete and having separate doors inside for accomodating all incomming / out going feeders of suitable sizes complete all as specified.
Incoming:-
(a) MCCB 4 Pole,200 amps ,415 Volt of breaking capacity not less than 25 KA (Ics=100 % of Icu) adjustable TM Setting (Optium 2.0) - 01 No.
(b) Copper Busbar 300A current rating duly sleeve insulated for set of 3 phase, 4 wire system - 01 Set.
Outgoing:-
(c) MCCB 4 Pole,100 amps ,415 Volt of breaking capacity not less than 25 KA (Ics=100 % of Icu) adjustable TM Setting (Optium 2.0) - 02 No.
(d) Digital type voltmeter of rating 0-500V
Digital Type Ampere meter of Rating 0-200A
(b) LED indicating Lamps R,Y,B-01 set
| 2.00 | Each Job |
| 4 | Supply, installations, testing and commissioning factory made out door cubical type LT panel board dust and vermin proof , free standing, floor mounting type mounted on and incluidng 1:3:6 PCC foundation as requried at site and of fabricated by 3.15 mm thick CRCA sheet over MS 40 X 40 X 5 mm thick angle iron frame of requried type for support with double door both sides open type with necessary locking arrangement with slopped roof on top duly painted with two coats of powder coated semense gray paint complete and having separate doors inside for accomodating all incomming / out going feeders of suitable sizes complete all as specified.
Incoming:-
(a) MCCB 4 Pole,250 amps ,415 Volt of breaking capacity not less than 25 KA (Ics=100 % of Icu) adjustable TM Setting (Optium 2.0) - 01 No.
(b) On load changeover of capacity 200A 4Pole
(c) Copper Busbar 400A current rating duly sleeve insulated for set of 3 phase, 4 wire system - 01 Set.
Outgoing:-
(d) MCCB 4 Pole,200 amps ,415 Volt of breaking capacity not less than 25 KA (Ics=100 % of Icu) adjustable TM Setting (Optium 2.0) - 02 No.
(f) MCB TPN 32 Amp, 415 V C series - 01 Nos
(g) Digital type voltmeter of rating 0-500V
Digital Type Ampere meter of Rating 0-200A
(h) LED Indicating Lamps R,Y,B - 01 Set | 2.00 | Each Job |
| 5 | Supply, installations, testing and commissioning factory made out door cubical type LT panel board dust and vermin proof , free standing, floor mounting type mounted on and incluidng 1:3:6 PCC foundation as requried at site and of fabricated by 3.15 mm thick CRCA sheet over MS 40 X 40 X 5 mm thick angle iron frame of requried type for support with double door both sides open type with necessary locking arrangement with slopped roof on top duly painted with two coats of powder coated semense gray paint complete and having separate doors inside for accomodating all incomming / out going feeders of suitable sizes complete all as specified.
Incoming:-
(a) MCCB 4 Pole,63 amps ,415 Volt of breaking capacity not less than 25 KA (Ics=100 % of Icu) adjustable TM Setting (Optium 2.0) - 01 No.
(b) Copper Busbar 100A current rating duly sleeve insulated for set of 3 phase, 4 wire system - 01 Set.
Outgoing:-
(c) MCCB 4 Pole,40A amps ,415 Volt of breaking capacity not less than 16 KA (Ics=100 % of Icu) adjustable TM Setting (Optium 2.0) - 05 No.
(d) Digital type voltmeter of rating 0-500V
(e)Digital Type Ampere meter of Rating 0-200A
(f) LED Indicating Lamps R,Y,B - 01 Set | 7.00 | Each Job |