| 1 | FIRE PUMP ROOM EQUIPMENT
Supplying, installing testing and commissioning of electrical motor driven Main Pump of horizontal centrifugal end suction backpull out type with gland packing and capable to deliver 2280 LPM at 70 Mtr Head with all necessary accessories like bronze impeller, stainless steel shaft along with anti-vibration mounting, coupling, coupling guard and base plate for pump, fabricated mild steel channel,foundation bolts, and pump should have the dry run sensor provision, etc., as per local fire brigade requirement . The pump shall capable to have 3.5 kg/cm residual pressure at top most hydrant point. The pump shall be coupled to electrical motor with speed of 2900 RPM, Electric supply 415V, 50 Hz and complete set shall be mounted on a common base frame. The quoted rate shall includes providing & fixing of coupling, coupling gaurd and Foundation bolts etc.Make- WILO/KIRLOSKAR/KSB | 1.00 | No. |
| 2 | Supplying, installing and commissioning of Diesel Engine driven common stand by pump, horizontal centrifugal end suction backpull out radiator cooling type with gland packing and capable to deliver 2280 LPM at 70 Mtr head with all necessary accessories like bronze impeller, stainless steel shaft along with anti-vibration mounting, coupling, gear box, base plate for pump, fabricated mild steel channel with foundation bolts etc., It includes providing and fixing fuel oil tank (capacity as perTAC requirements) with supports and necessary pipe works for diesel engine, battery and battery charger to be connected to control panel of diesel engine and exhaust silencer including necessary pipe work and lagging, pump should have the dry run sensor provision, etc., and shall be automatic in operation with diesel engine control diesel engine control panel with 24V DC storage battery & its battery charger with required Ampere - hour rating, terminal box (2 nos. of 12volts), as per TAC including all associated electrical works. Make- WILO/KIRLOSKAR/KSB | 1.00 | No. |
| 3 | Supplying, installing and commissioning of electrical motor driven Jockey pump of horizontal centrifugal end suction backpull out type with gland packing and capable to deliver 180LPM (10.8 m / Hr) at 70 MWC with all necessary accessories like bronze impeller, stainless steel shaft along with anti-vibration mounting pad and flexible connections at discharge end of the pipes, pump should have the dry run sensor provision etc. and shall be automatic in operation.The pump shall be coupled to motor of with speed of 2900RPM and complete set shall be mounted on common base frame. The quoted rate shall includes providing & fixing of coupling, coupling gaurd and Foundation bolts etc. Make- WILO/KIRLOSKAR/KSB | 1.00 | No. |
| 4 | S/I/T&Commissioning of LT indoor floor mounted cubical type electrical fire fighting panel made out by 2mm CRCA steel sheet duly derusted & painted by Red out & inside gray powder cote paint is designed as G.A drawing. (FOR FIRE FIGHTING) as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list.40 kA Type 2 3P+N SPD alongwith 63A, 4P MCB, C series, 10 kA shall be installed in the incomer. 40X10MM Separate Aluminium Earth bus bar should be installed.
INCOMING: One(1)- 200 Amp 25 KA TP with solid neutral SDFU with HRC fuses 3 nos (Make-Legrand/Siemens/Schneide/ABB) including 01 no of MFM with RS 485, 3 Nos 200/5 metering CTs of Class 1.0, ON/ OFF indicating lamps, 3 Nos Phase indicating lamp and SP 6A MCB ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB200). . Busbar- 04 numbers of 300Amps 50kA Electrolytic copper busbar duly sleeved by color coaded PVC sleeve & supported by suitable size DMC insulator.
OUTGOING: a)One(1)-160 Amp 25kA TP MCCB with ROM 25kA with adjustable THERMAL Release with Ics=100% Icu. ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA), along with star delta starter incorporating 3 nos Power 3P contactor with top add on(2NO+2NC) ,Bimetal OLR of suitable rating,axulary contactor , ON/ OFF push button, ON/ OFF indicating lamp, 3 Nos CTs metering CTs 250/5, Ammeter .
b) 1 No (Outgoing) 63 Amp 25kA TP MCCB with ROM 25kA with adjustable THERMAL Release with Ics=100% Icu. ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA), along with star delta starter suitable for motor with O/L release, ON/ OFF push button, ON/ OFF indicating lamp,3nos 100/5 CT,Ammeter,S/S
c) 1 Set Relay, Auto/ Manual Selector Switch, Battery Charger, Annunciation Panel,hotor, Control wiring of pressure switches, flow switches and starters etc as required for auto and manual operation of Jockey pumps, Main Electric Pumps and Diesel Engine Pump as per direction of Engineer-in-charge.d)1 lot control wiring from pressure switch to panel board through auxiliary contactor with 1.5 sq. mm unarmoured PVC insulated ,PVC sheathed copper cable etc as required. | 1.00 | No. |
| 5 | Supplying, laying, testing & commissioning of FRLS, XLPE insulated, PVC outer sheateh, steel armoured, aluminium conductor, 1100v grade power cables with glands etc. The cables shall be laid in tray / Hume pipe / in trenches/on walls/ floor etc. as required. For cables laid out door the rate shall include earth excavation providing brick and sand protection, refilling and compacting the earth.The rate shall excludes tray & Hume pipes. The quoted rate shall includes the end termination for 1.1KV cables with double compression type cable gland and heavy duty tinned copper cable sockets as per the relevant IS standards. Rate shall be inclusive of all sundry materials like adhesive tape , PVC sleeves , bolts and nuts, washers etc. including plugging unused holes. The minimum size of the cables shall as mentioned below,Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Gloster
3 core x 35 sqmm aluminium conductor cable | 56.00 | Rmt |