Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 4087292 |
|---|---|
| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Special Repair Of Ht Line For Msl Shed At Amn Point At Mil Stn Bhuj Under Ge (army) Bhuj |
| Last Date For Submission | 29th May, 2026 |
| Opening Date | 02 Jun, 2026 |
| Document Cost | 500.00 |
|---|---|
| EMD | 78800.00 |
| Estimated Cost | 3940000.00 |
| City | Bhuj |
|---|---|
| State | Gujarat |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Supply, installation, testing & commissioning of Outdoor (IP54) 11kV 630Amps 21KA/3 sec. One side Extensible 6 Way Ring Main Unit Compact switchgear consisting of 4 nos. fixed motorized Vacuum Circuit Breaker Module and Copper Busbar in SF6 insulated stainless steel enclosure (2.5 mm thick, SS304 grade). The complete RMU must be type tested for Internal arc 21KA for 1 sec with AFLR Classification for Gas tank & Cable Chamber. HT RMU shall preferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. The Vaccum Interrupter must RMU manufacturer's own make. The complete RMU shall be consisting of followings: (a) All VCB module shall have Auxiliary powered numerical protection relay (RMU manufacturer's own make) having Over Current, & earth fault protection with Modbus protocol (RS485) complaint with programable 6 DO, 4DI & 8 front LED with additional 3 nos fixed front LED. Relay shall have CB ON-OFF function key & 20 nos disturbance recording. (b) Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. (c) SF6 Gas pressure indicator on the gas tank. (d) Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO amd suitable for 10000 mechanical operation. (e) CT shall be minimum 40/1A ,2.5VA , 5P20 - 3 nos. for protection (f) Right angle boot to be provided in each module (g) 2X12V, 26AH Battary with Charger - 1 Set (h) Auxiliary VT shall be 11KV/230V, 500VA for AC supply input to Battary Charger. (j) Platform/Staging shall be provide as per OEM Reccommendation/OEM drawing. (k) The rate of RMU including all accessories and staging shall be included in quoted rates. | 1.00 | Each Job |
| 2 | Supply, laying & testing HT Cable XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with aluminum Conductor, 11000 volts grade cross sectional area of size 95 sqmm 3 Core complete all as specified and as directed. | 1165.00 | RM |
| 3 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc for laying of cables, erection of poles, struts/ stays etc not exceeding 10 sqm on plan and getting out in any type of soil complete all as specified and as directed. Note: Rate for removal and disposal of bushes and roots etc where applicable during the work shall be included in the quoted rate complete all as specified and as directed. | 335.50 | CUM |
| 4 | Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil complete all as specified and as directed. | 224.00 | CUM |
| 5 | Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point in soils complete all as specified and as directed. | 111.60 | CUM |
14 Days Left