| 1 | Supply, installation, testing & commissioning in replacement LT panel board In door type, wall mounted of suitable size for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of CRCA sheet outer box thickness 2.0 mm, side covers with hinged doors & proper locking arrangement, rubber gasket on front and back door to make it dust and vermin proof, powder coated , The cubicle shall have control wiring with minimum size: 1.5 SQmm of copper cable including M&L for fixing / grouting the panel to wall and required cable connection with necessary double compression brass gland and cable end sockets, complete comprising of following accessories all as specified and any other items required for smooth functioning of VFD starter Panel is deemed to be included in the rate quoted for the items and as directed by the Engr-in-charge.
Note:-All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job.) also having built in single phase preventer for 5 HP capacity fan motor complete with following specifications:-
| 5 | Each Job |
| 2 | INCOMING:-
(i) MCB 25A 10kA (incoming)-01 No.
(ii) Ammeter, Voltmeter and CTs- 01 set
(iii) RYB indicating lamps LED type- 03 Nos
(iv) MCB SP 6A -03 Nos
OUTGOING:-
(i) FASD Starter 5 HP -01 No.
(ii) Contactor 3P 12 A -03 No.
(iii) O/L relay 6-10A -01 No.
(iv) ON-TRIP indicator - 02 No.
(v) Start/stop push button - 02 No.
(vi) MCB SP 6A,10kA- 01 No
(vii) Add on Aux Block 1 NO + 1 NC - 02 set
(viii) Single Phase Preventer - 01 No
(ix) Auto manual selector switch - 01 No.
(x) Star Delta Timer - 01 No.
(xi) Variable Frequency Drive suitable for 5 HP motor -01 No.Make:- Danfoss
(xii) Glass relay 5 A, 11 PIN -01 No.
(xiii) Control Wiring, busbar,nut, bolts, washers , auxillary contacts etc alongwith all misc connected items are deemed to be included in quoted rate.
Note:- Contractor need to submit drawing of panel alongwith bill of quantities for approval before starting execution of work | | |
| 3 | Supply, installation, testing & commissioning in replacement LT panel board In door type, wall mounted of suitable size for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of CRCA sheet outer box thickness 2.0 mm, side covers with hinged doors & proper locking arrangement, rubber gasket on front and back door to make it dust and vermin proof, powder coated , The cubicle shall have control wiring with minimum size: 1.5 SQmm of copper cable including M&L for fixing / grouting the panel to wall and required cable connection with necessary double compression brass gland and cable end sockets, complete comprising of following accessories all as specified and any other items required for smooth functioning of VFD starter Panel is deemed to be included in the rate quoted for the items and as directed by the Engr-in-charge.
Note:-All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job.) also having built in single phase preventer for 7.5 HP capacity fan motor complete with following specifications:- | 5 | Each Job |
| 4 | INCOMING:-
(i) MCB 32A 10kA (incoming)-01 No.
(ii) Ammeter, Voltmeter and CTs- 01 set
(iii) RYB indicating lamps LED type- 03 Nos
(iv) MCB SP 6A -03 Nos
OUTGOING:-
(i) FASD Starter 7.5 HP -01 No.
(ii) Contactor 3P 18 A -03 No.
(iii) O/L relay 9-15A -01 No.
(iv) ON-TRIP indicator - 02 No.
(v) Start/stop push button - 02 No.
(vi) MCB SP 6A,10kA- 01 No
(vii) Add on Aux Block 1 NO + 1 NC - 02 set
(viii) Single Phase Preventer - 01 No
(ix) Auto manual selector switch - 01 No.
(x) Star Delta Timer - 01 No.
(xi) Variable Frequency Drive suitable for 7.5 HP motor -01 No.Make:- Danfoss
(xii) Glass relay 5 A, 11 PIN -01 No.
(xiii) Control Wiring, busbar,nut, bolts, washers , auxillary contacts etc alongwith all misc connected items are deemed to be included in quoted rate.
Note:- Contractor need to submit drawing of panel alongwith bill of quantities for approval before starting execution of work | | |
| 5 | Supply, installation, testing & commissioning in replacement LT panel board In door type, wall mounted of suitable size for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of CRCA sheet outer box thickness 2.0 mm, side covers with hinged doors & proper locking arrangement, rubber gasket on front and back door to make it dust and vermin proof, powder coated , The cubicle shall have control wiring with minimum size: 1.5 SQmm of copper cable including M&L for fixing / grouting the panel to wall and required cable connection with necessary double compression brass gland and cable end sockets, complete comprising of following accessories all as specified and any other items required for smooth functioning of VFD starter Panel is deemed to be included in the rate quoted for the items and as directed by the Engr-in-charge.
Note:-All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job.) also having built in single phase preventer for 7.5 HP capacity fan motor complete with following specifications:- | 6 | Each Job |