| 3 | Supply, Installation, Testing and Commissioning (SITC) of floor mounted LT Control Panel suitable for operation of Three Nos. Submersible Pump Sets up to 10 HP each, suitable for 415 Volts, 3 Phase, 50 Hz, 4 Wire AC supply system.
The panel shall be fabricated from 16 SWG M.S. sheet steel of welded construction, dust, damp and vermin proof, floor mounted type, complete with double front doors, 14 SWG hinges, locking arrangement, gland plates, cable alley, bus-bar chamber, powder coating and mounted on 600 mm high base frame fabricated from 50 mm 50 mm 6 mm M.S. angle iron.
The panel shall consist of the following:
A. COMMON INCOMER
1. MCCB, 160 Amp, 4 Pole, adjustable thermal magnetic type 1 No.
2. RCCB/ELCB, 160 Amp, 4 Pole with earth fault indication and positive contact indication 1 No.
3. Copper Bus Bar System of suitable capacity with colour coded sleeves 1 Set.
4. Digital Ammeter (96 mm 96 mm) with selector switch and CTs 1 No.
5. Digital Voltmeter (96 mm 96 mm) with selector switch 1 No.
6. R-Y-B LED Indicating Lamps 1 Set.
7. Neutral Link and Earth Bar 1 Set.
B. PUMP FEEDER NO. 1
1. Fully Automatic Star Delta Starter suitable for 10 15 HP Motor 1 No.
2. Motor Protection Assembly comprising (Earth Leakage, Phase Sequence, Single Phasing, Overload, High & Low Voltage Protection) 1 Set.
3. Programmable Time Switch with Auto/Manual operation 1 No.
4. 5 KVAR Capacitor with TP Isolator 1 No.
C. PUMP FEEDER NO. 2
1. Fully Automatic Star Delta Starter suitable for 10 15 HP Motor 1 No.
2. Motor Protection Assembly comprising (Earth Leakage, Phase Sequence, Single Phasing, Overload, High & Low Voltage Protection) 1 Set.
3. Programmable Time Switch with Auto/Manual operation 1 No.
4. 5 KVAR Capacitor with TP Isolator 1 No.
D. PUMP FEEDER NO. 31. Fully Automatic Star Delta Starter suitable for 10 15 HP Motor 1 No.2. Motor Protection Assembly comprising (Earth Leakage, Phase Sequence, Single Phasing, Overload, High & Low Voltage Protection) 1 Set.3. Programmable Time Switch with Auto/Manual operation 1 No.4. 5 KVAR Capacitor with TP Isolator 1 No.
E. COMMON ACCESSORIES1. Internal wiring using FRLS copper control wires complete with ferruling, thimbling and identification tags.2. Copper earthing strip and earth terminals.3. Cable glands, lugs, hardware and mounting accessories.4. Danger notice plate, engraved name plate and schematic diagram.5. Testing, commissioning and trial run complete.The panel shall be suitable for independent operation of any one pump or simultaneous operation of all three pumps. All switchgear/components shall be of DJB approved make and ISI marked wherever applicable | 3 | Set |