Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 4860530 |
|---|---|
| Organisation Name | Delhi Jal Board |
| Tender Brief | Supply, Installation, Testing and Commissioning Of 500 Sq Mm Aluminum Armoured Cable With Allied Works For New 400 Kva Diesel Generator Set At Varunalaya Phase-ii Substation Djb Hq Jhandewalan |
| Last Date For Submission | 13th Jul, 2026 |
| Opening Date | 13 Jul, 2026 |
| Document Cost | 500.00 |
|---|---|
| EMD | 11500.00 |
| Estimated Cost | 0.00 |
| City | Delhi |
|---|---|
| State | Delhi |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Fabrication of new LT panel board having sheet enclosure made out of 16 SWG sheet and 50 x 50 x6 mm angle iron and size 1800 x 750 x 450 mm totally enclosed, powder coated free standing, floor mounted type, dust & vermin proof, out ward opening lockable door having hidden hinges and The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible wire of 1.5 mm2 each wire will be terminating a ferule crimped to the wire CT as per the requirement having the following components.:-MCCB 415V, 3 phase 50Hz, 630 Amp, 50 ka breaking capacity with handle & Spreader - Make L&T/Siemens/DJB Approve Make-01 NoOn load change over switch 4 Pole 630 Amp. Open execution type with handle & Spreader Make L&T/Siemens/DJB Approved Make-01 No Digital Ampere meter with selector switch Make L&T/AE/DJB Approved Make- 03 Nos Digital Voltmeter with selector switch Make AE/L&T/DJB Approved Make-01 No Selector Switch for Voltmeter Make AE/L&T/DJB Approved Make -01 NoIndicating Light (RYB)-01 Set | 1 | Job |
| 2 | Supply of single core 500 Sq. mm. Aluminium Conductor Power Armoured Cable. Havells/Grandlay/National/ DJB Approved Make | 200 | Mtr |
| 3 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required above 185 sq. mm and upto 500 sq. mm DSR Code 7.6.4 | 200 | Meter |
| 4 | Excavation for the cable trenches in hard rock not exceeding 1.5 Meters in width, and lift upto 1.5 Meters, including getting out the excavated soil, and disposal of excavated soil as directed within a lead of 50 Meters & refilling with soil & RCC work as per site requirement. DSR 14.6 | 56 | cum |
| 5 | Installation, Testing and commissioning of panel, Cable & allied accessories as per required parameters. | 1 | Job |
6 Days Left