| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Repair/ Maintenance Of Distribution Of Transformer, Ht 11 Kv Rmus, Lbs, 4 Pole Structure, Certain Diversion Of Underground Cable And Other Connected Works At Ina Ezhimala |
| Last Date For Submission | 30th Jun, 2026 |
| Opening Date | 07 Jul, 2026 |
| Document Cost | 500.00 |
|---|---|
| EMD | 100000.00 |
| Estimated Cost | 5000000.00 |
| City | Ezhimala |
|---|---|
| State | Kerala |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | M&L for servicing of HT 11 KV, RMU any type and make by carry out the following work once in six months :- (i) Cleaning/decarbonizing of all levers, springs using suitable cleaning agent and tightening of screws, nuts, bolts, spring etc for proper functioning. (ii) Lubricating/greasing of all operating mechanism and moving parts, switching & tripping mechanism, demoisturing of all parts. (iii) Testing of relay tripping performace of RMU. (iv) Checking of all relays and interlocking if any. (v) Caiberation, performance testing using primary injection method and necessary adjustment of relays for successful operation at the time of fault occurence etc. (vi) Checking of operating mechanism adjustments, measurements of the mechanical clearances of operating mechanism, internal wiring circuit etc, tightening of all connections, replacement of unserviceable fuse/MCB SP including removing moisture deposit inside the RMU. (vii) Checking all end terminals, tightening the nut, bolt and washers, replace the unserviceable nut, bolt & washers, engage the RMU with the supply system and testing for smooth functioning complete all as specified and as directed by the Engineer in charge. Note : (i) The cost of cleaning materials, HT Tape, thinner, cotton waste, monoplast, unserviceable cable end socket, steel nuts, bolts with double washers, MCB SP upto 32 Amp, replacement of complete HT packing/gasket shall deemed to be included in the quoted rate. (ii) Contractor shall be isolated and earth the breaker before start the work. | 36.00 | Each |
| 2 | S&F in repair self power protection relay, 220 V having 400 A current capacity, 4 poles suitable for fixing in RMU and CSS having digital type screen complete all as specified and as directed. | 4.00 | Each |
| 3 | S&F in replacement 3 phase digital Multi function meter 440 V with energy standard : IEC62053-22 CLASS 0.5 s FOR ACTIVE ENERGY AND IEC 62053-23 CLASS 1.0 for reactive energy suitable for fixing in RMU/CSS with complete wiring system all as specified and as directed. | 12.00 | Each |
| 4 | S&F in replacement of 12V battery, 12 AH, 10.5 V and boost charging voltage 14.0 V per bloc @25 degree C suitable for charging the RMU including necessary wiring as required and as directed. | 12.00 | Each |
| 5 | S&F in replacement battery charger suitable for existing RMU for 12V battery including all wiring connection for smooth functioning of RMU complete all as specified and as directed. | 2.00 | Each |