Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 4364772 |
|---|---|
| Organisation Name | Public Works Department |
| Tender Brief | Corrigendum : Infrastructural Development Upgradation Bwo Installation High Mast Lights Genset In Fandv Market Ganderbal B.w.o Electric Work (electric Part) |
| Last Date For Submission | 8th Jun, 2026 |
| Opening Date | 09 Jun, 2026 |
| Document Cost | 800.00 |
|---|---|
| EMD | 39362.00 |
| Estimated Cost | 1968110.00 |
| City | Ganderbal |
|---|---|
| State | Jammu and Kashmir |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Part-A(Panel & Cabling ) | ||
| 2 | Design/Supply/Installation/Testing and commissioning of distribution/feeder outdoor panel having a sloped roof (3+1) Al. bus bar( Bus Bar shall be insulated with heat shrinkable sleeves and shall be colour coded having minimum size 20 mm x 10 mm with spacing as per latest IE Standards) of cubical type vermin proper double door lockable outdoor type fabricated out of 14/16 SWG MS Sheets powder coated weather proof, dust proof with IP 65 protection with angle iron stand of 2.5 feet height/ground clearance properly grouted in cement concrete of 1:2:4 ratio-filter with baby insulators/glands/thimbles suitable for use at 415 Volts 3 Phase,4 wire 50Hz system complete in all respects complete in all respects with following: Incomer: 400 Amp TPN MCCB Adjustable Type with 50 kA Breaking capacity of L&T /ABB /Legrend /Simens make = 1 No. Digital Multi function Volt Meter with C T of proper ratio. = 1 set indicators = 3 no. Outgoing: 630 Amps TPN Aluminium Bus Bar = 1 Set The Panel manufacturing unit should be CPRI Registered with latest ammended IEC / IS 61439 and the Contractor has to submit the test certificate of main switch gear's and Drawing's of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards ) & is to approved by Department not less than the rank of SDO before manufacturing of panel. | 1 | No |
| 3 | ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER ROD EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value.Supply,Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 20mm Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through suitable DWC High Density Poly ethylene Pipe having Corrugation complete job. | 1 | No |
| 4 | Supply/Excavation/Laying/Testing and Commissioning of 3.5-Core 120 mm sq. Al armored PVC cable withstand voltage of 650/1100V ISI Marked. Havells/Polycab/RR-Kabel/KEI Make. IIncluding Supply/Laying of HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (01 Ft below ground level) including excavation and refilling the trench of standard make as approved.The cable shall include end termination lugs with its crimping /taping.(Sub-Station to Main Panel) | 30 | Mtr. |
| 5 | Design,Fabrication,Supply, Installation, Testing and Commissioning of Main LT Control outdoor slopped Roof,Double Door panel Floor Mounted fabricated of 16 gauge sheet steel,the panel should have standing dust & vermin proof with gasket lockable door of 16 gauge sheet steel with angle iron stand of 2.5 feet height/ground clearance properly grouted in cement concrete (If Required) of 1:2:4 ratio-filter . The Panel should be painted with Electro static powder coated colour, Siemens grey structural with proper chemical pre-treatment with film thickness 35-40 Microns,duly fitted with Voltmeter, R/Y/B Phase-indicators etc with baby insulators/glands/thimbles suitable for use at 415 Volts 3 Phase,4 wire 50Hz system complete in all respects complete in all respects with following:- Incoming: 1) 250 Amp-4 pole,50kA MCCB with extended terminals Adjustable Thermal & Fixed Magnetic with ROH Switch L&T/ABB/Legrand/Simens Make = 01 No. 2) 200 Amp-4 pole,50kA MCCB with extended terminals Adjustable Thermal & Fixed Magnetic with ROH Switch L&T/ABB/Legrand/Simens Make = 01 No. Generator: 200 Amp Changerover ROH Switch Legrand/L &T/ABB Make including S/F/Crimping of Suitable Size of thimbles for connections ByPass Switch: 3-Phase, Four Pole 200 Amp,415V Ac,50Hz,Rotatory Handle bypass Switch Legrand/L &T/ABB/Equivalent Make including S/F/Crimping of Suitable Size of thimbles for connections as per site requirement for bypassing AVR. as approved. Outgoing: 600 Amp Suitable Al. Bus bar = 01 Set , 160 Amp 4 pole,36kA MCCB with extended terminals Adjustable Thermal & Fixed Magnetic with ROH Switch L&T/ABB/Legrand/Simens Make = 02 No. for 02 Ckts. Panel shall have provision for entry of cables from the bottom as required. The Panel manufacturing unit should be CPRI Registered with latest ammended IEC / IS 61439 and the Contractor has to submit the test certificate of main switch gear's and Drawing's of panel (Showing claerly dimensions of panel with spacing of switchgear as per IE Standards ) & is to approved by Department not less than the rank of SDO before manufacturing of panel. | 1 | No |
4 Days Left