| 1 | FIRE DETECTION SYSTEM- FASSupply, installation, testing & commissioning of Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 event plus 1000 alarm log history events, QWERTY keypad for programming. The panel should be equipped with sufficient numbers of loops considering 20 Percentage spare capacity in each loop. Each loop shall have a capacity of minimum 300 analog addressable devices. The panel shall work in degrade mode in case of CPU failure, Products not having this feature may offer Redundant CPU. Four access levels, flash EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. with 10 Loop card Designed to meet UL864, 10th Edition. The panels shall be supplied with necessary Network Interface, TCP/IP Card and Bacnet Modules for integration with Central Command Stations.Rates as per Vidhansabha renovation item no-605.1Make: Notifier, Esser, Gamewell, Eltek, Gent or its equivalent | 10.000 | Nos |
| 2 | Supply, installation, testing & commissioning of Microprocessor based 2 loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with minimum 80 characters LCD display, 800 event plus 200 alarm log history events, QWERTY keypad for programming. The panel should be equipped with sufficient numbers of loops considering 20 Percentage spare capacity in each loop. Each loop shall have a capacity of minimum 300 analog addressable devices. The panel shall work in degrade mode in case of CPU failure. Four access levels, flash EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. The panels shall be supplied with necessary Network Interface, TCP/IP Card and Bacnet Modules for integration with Central Command Stations. Approved make-Notifier-NFS 2-640 / Kidde Fenwal / GamewellRate as per quotationMake: Notifier, Esser, Gamewell, Eltek, Gent or its equivalent | 4.000 | Nos |
| 3 | Supply, installation, testing & commissioning of required suitable interface card for Bacnet Interface, network component and cabling work for Seamless integration with existing panels installed at Block- 1 & 2 without any external module in a such a way that all panels are peer-to-peer networked and data for complete system shall be mapped on Network repeater panel to be installed at Block no.7 & Block 14, Ground floor. Rate as per quotationMake: Notifier, Esser, Gamewell, Eltek, Gent or its equivalent | 5.000 | Nos |
| 4 | Supply, installation, testing & commissioning of required suitable interface card for TCP/IP Interface, network component and cabling work for Seamless integration with existing panels installed at Block- 1 & 2 without any external module in a such a way that all panels are peer-to-peer networked and data for complete system shall be mapped on Network repeater panel to be installed at Block no.7 & Block 14, Ground floor. Rate as per quotation Make: Notifier, Esser, Gamewell, Eltek, Gent or its equivalent | 5.000 | Nos |
| 5 | Supply, installation, testing & commissioning of required network card for all the Fire Alarrn nodes including TCP/IP & Bacnet Interface, network component (Media conevertors, Patch cords and OFC Splicing) for Seamless integration with existing panels installed at Swarnim Sankul 1 & 2 and vidhansabha without any external module in a such a way that all panels are peer-to-peer networked and data for complete system shall be mapped on Network repeater panel to be installed at Block no.14, Ground floor. Rate as per quotationMake: Notifier, Esser, Gamewell, Eltek, Gent or its equivalent | 41.000 | Nos |