| 1 | Supply, installation, testing and commissioning of floor mounted LTOUTDOOR feeder pillar box AC 415V,50 HZ 3 Phase 4 wire of suitable size for accomodating the following accessories totally enclosed self supporting structure /cubicle, fully compartmentalized type O/P terminal of suitable capacity, suitable foroutdoor use, withbottom cable entry with suitable cable glands structure made out of 2mm thick outer body and inner partition 1.5mm thick hinged doors atfront with suitable locking arrangement ,with CPRI report tested forIP55, made ofCRCA steel sheet of suitable Size with angle ironframe work and legs of ISA 50X50X5 mm, with four legs with suitable mounting arrangement for copper bus bars of suitable capacity i.e 600 Amps structure treated under 8-tank metal treatment process and duly powder coated orepoxy coated, dimension :1500 X1200 X600 mm (HXWXD) complete all as specified and as directed.
INCOMER :-
(a) MCCB 250 Amp, 4 pole 415 Volts with microprocessor controller of breaking capacity 36KA with adjustable thermal and magnetic settings, with Spreaders links & Rotary Handle- 01 Nos
(b) Digital MFM 96sqmm Cl 1 - 1 nos
Item continued below as srl item No.1.10
| 1.00 | Each Job |
| 2 | Item continued from srl item No.1.00 here-in-above
(c) CT coil 400/5 Cl. 1, 15va tape wound - 3 nos
(e) LED Indicator 22.5mm dia RYB - 1 set
(f) MCB 32A SP 10ka 'C' series - 3 nos
(g) Manual Change Over Switch 250A 4Pole - 1 nos
Outgoing:- (i) MCCB 125 Amp, 4P, 25KA with adjustable thermal and magnetic setting with Spreaders links & Rotary Handle - 4 nos
(ii) MCCB 250 Amp, 4P,25KA with adjustable thermal and magnetic setting with Spreaders links & Rotary Handle -1 nos
BUSBAR :-(Outgoing)
(i) Copper Bus-bar 600 Amps , supported on non hygroscopic fibres and brass screws for mounting - 04 Nos - 1 set
Note: (a) Internal Incomer MCCB and Outgoing MCCB Connected through solid Copper bus bar.
(b) MISCELLANEOUS Viz. wires, Sockets, terminals, din channels, nuts & bolts.-1 lot
(c) Technician charges for internal wiirng - 1 set
(d) Electrical Panel Boards IP55 - 1 nos
| | |
| 3 | Supply, installation, testing and commissioning of floor mounted LTOUTDOOR feeder pillar box AC 415V,50 HZ 3 Phase 4 wire of suitable size for accomodating the following accessories totally enclosed self supporting structure /cubicle ,fully compartmentalized type O/P terminal of suitable capacity, suitable foroutdoor use,withbottom cable entry with suitable cable glands structure made out of 2 mm thick outer body and inner partition 1.5mm thick hinged doors atfront with suitable locking arrangement ,with CPRI report tested forIP55, made of CRCA steel sheet of suitable Size with angle ironframe work and legs of ISA 50X50X5 mm ,with four legs with suitable mounting arrangement for copper bus bars of suitable capacity i.e 1000 Amps structure treated under 8-tank metal treatment process and duly powder coated orepoxy coated ,Minimum box dimension :1500 X2650 X400 mm (HXWXD), complete all as specified and as directed.
INCOMER :-
1.1(a) MCCB 630 Amp ,4 pole 415 Volts with microprocessor controller of breaking capacity 36KA with adjustable thermal and magnetic settings, with Spreaders links & Rotary Handle- 01 Nos
Item continued below as srl item No.2.10
| 1.00 | Each Job |
| 4 | Item continued from srl item No.2.00 here-in-above
1.2 Digital MFM 96sqmm Cl 1. - 1 nos
1.3 CT coil 400/5 Cl. 1, 15va tape wound - 3 nos
1.4 LED Indicator 22.5mm dia RYB - 1 set
1.5 MCB 32A SP 10kA 'C' series - 3 nos
1.6 Manual Change Over Switch 630A 4Pole - 1 nos
Outgoing:-
1.7(i) MCCB 125 Amp, 4P, 25KAwith adjustable thermal and magnetic setting with Spreaders links & Rotary Handle - 3 nos
(ii) MCCB 160 Amp, 4P,25KAwith adjustable thermal and magnetic setting with Spreaders links & Rotary Handle -1 nos
(ii) MCCB 250 Amp, 4P,25KAwith adjustable thermal and magnetic setting with Spreaders links & Rotary Handle -1 nos 1.8 BUSBAR :-(Outgoing)
(i) Copper Bus-bar 1000 Amps , supported on non hygroscopic fibres and brass screws for mounting - 04 Nos -1 set
1.9 Note: Internal Incomer MCCB and Outgoing MCCB Connected through solid Copper bus bar.
2.1 MISCELLANEOUS Viz. wires, Sockets, terminals, din channels, nuts & bolts.-1 lot
2.2 Technician charges for internal wiirng - 1 set
2.3 Electrical Panel Boards IP55 - 1 nos
| | |
| 5 | Supply, installation, testing and commissioning of floor mounted LTOUTDOOR feeder pillar box AC 415V,50 HZ 3 Phase 4 wire of suitable size for accomodating the following accessories totally enclosed self supporting structure /cubicle ,fully compartmentalized type O/P terminal of suitable capacity, suitable foroutdoor use,withbottom cable entry with suitable cable glands structure made out of 2 mm thick outer body and inner partition 1.5mm thick hinged doors atfront with suitable locking arrangement ,with CPRI report tested forIP55, made of CRCA steel sheet of suitable Size with angle ironframe work and legs of ISA 50X50X5 mm ,with four legs with suitable mounting arrangement for copper bus bars of suitable capacity i.e 1000 Amps structure treated under 8-tank metal treatment process and duly powder coated orepoxy coated ,Minimum box dimension :1500 X1400 X400 mm (HXWXD), complete all as specified and as directed.
INCOMER :-
1.1(a) MCCB 630 Amp,4 pole 415 Volts with microprocessor controller of breaking capacity 36KA with adjustable thermal and magnetic settings, with Spreaders links & Rotary Handle- 01 Nos
Item continued below as srl item No.3.10
| 1.00 | Each Job |