| Organisation Name | Nuclear Fuel Complex |
| Tender Brief | Corrigendum : Supply, Installation, Testing and Commissioning Of 11kv Substation Works For Tube Plants Load Centre At Nfc, Hyderabad |
| Last Date For Submission | 3rd Jul, 2026 |
| Opening Date | 06 Jul, 2026 |
| Document Cost | 0.00 |
|---|---|
| EMD | 1700000.00 |
| Estimated Cost | 85000000.00 |
| City | Hyderabad |
|---|---|
| State | Telangana |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of 11KV, 1250 A, 26.3 KA/3 sec short circuit rated , 26.3 KA/1 sec Arc Flash rated , Totally Type Tested, LSC2B, HV indoor draw out type metal enclosed switchboard with Copper busbars incorporating Vacuum Circuit breakers, line PT, complete with CTs, PTs, Multi function meters (MFMs), metering and numerical relays and all other accessories like lifting truck, earthing truck, commissioning spares etc complete. The switchgear shall be fabricated as per latest IS and tender specifications 1250A VCB-2 No as Incomer 1250A VCB - 1 No as Buscoupler 1250A VCB- 1 Nos as Tie Feeder 1250A VCB- 9 Nos as Outgoings All feeders shall be provided with numerical relays with IEC 61850 protocol, digital multi function meters to indicate voltage, current, power, energy, power factor; Analog ammeters with selector switch and On/Off/Trip Indication Lamps | ||
| 2 | Supply | 1 | Set |
| 3 | Installation | 1 | Set |
| 4 | Supply, installation, testing and commissioning of 11/0.433KV 2500KVA 3 phase, 50Hz, Dyn11 indoor step down Cast Resin transformer with 8% Impedance, ECBC Energy effeciency rating, Air Natural cooling, Off circuit tap changer with a range of - 7.5% to + 7.5% in steps of 2.5% on HT side and other accessories as listed in the specifications. The transformer shall be suitable for bus duct termination on LV side and shall be provided with cable termination chamber on HV side. The Marshalling box shall be SCADA Compatible with Digital outputs.The CTs required for Restricted earth Falt Protection shall also be provided. The transformer shall be as per technical specification attached and in compliance with IS 2026, IS 10028, latest CPWD and CBIP specifications and latest ECBC code. Note: Trasformer shall be mounted on existing foundation | ||
| 5 | Supply | 3 | Nos |