Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 4234334 |
|---|---|
| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Repair/replacement And Maintenance Of External Electric Supply System At Af Station Jaipur |
| Last Date For Submission | 5th Jun, 2026 |
| Opening Date | 10 Jun, 2026 |
| Document Cost | 500.00 |
|---|---|
| EMD | 19600.00 |
| Estimated Cost | 980000.00 |
| City | Jaipur |
|---|---|
| State | Rajasthan |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Dehydration/Filteration of tranformer/Stabilizer oil at site by means of centrifuging machine in order to improve dielectric strength of oil as per IS-355. Break down voltage should not be less than 50 KV with 2.5 mm gap complete all as specified and as directed. | 4675.00 | Per Ltr |
| 2 | (a) Oil topping up shall be measured and paid seperately. | ||
| 3 | (b) Contractor has to make his own arrangement for oil filteration plant for both Technical and Domestic area. | ||
| 4 | (c) Contractor will have to produce and submit the test certificate of oil testing carried out in presence of user and Engineer in Charge or JE E/M. | ||
| 5 | M & L for topping up/change oil for transformer/stabilizer of 11KV/433 Volt of different capacity of dielectric strength /repturing capacity of oil not less than 50 KV (tested at site with testing kit with 2.5 mm gap ) and test the the dielectric strength of transformer oil before and after the topping up and make oil to the required level of transformer indicator level all as specified and directed. Make: Power/Savita or as approved by AGE(I). | 440.00 | Per Ltr |