#ItemQtyUnits
1Material and Labour for disconnecting defective transformer 33 KV/11 KV of capacity 3150 KVA from foundation and transportation the transformer for repair to authorized workshop/ factory, dismantling the transformer for repair and reassembling the same after repairs checking with phase to phase, phase to neutral with body & neutral earthing for proper result and connecting all connections properly with checking of oil level, silica gel, air release plug, gate valve, drain valve, bushing terminal, tapping changer etc and replacement of unserviceable parts, denting, welding, etc and spray painting with two coats of synthetic enamelled paint (grey paint) including preparation of surface, marking of MES No. with white paint of suitable size and transportation from workshop/ factory to site and re-installed on platform commissioning and testing of transformer upto entire satisfaction of Engineer-in-charge. Note :- (i) Quoted rate will be inclusive of labour for rewinding of complete transformer. (ii) Spare parts / transformer oil / copper for rewinding will be measured and paid separately. 1.00Each Job
2M&L for taking out unserviceable complete coil on limb and HV winding of transformer 33 KV/11 KV capacity 3150 KVA with suitable size/ existing gauge supper enamelled copper winding wire insulated with necessary insulating material complete all as specified & directed by Engineer-in-charge.495.00Kgs
3M&L for taking out unserviceable complete coil on limb and LV winding of transformer 33 KV/11 KV capacity 3150 KVA with suitable size/ existing gauge supper enamelled copper winding wire insulated with necessary insulating material complete all as specified & directed by Engineer-in-charge.495.00Kgs
4M&L for replacement of unserviceable HT bushes insulators of transformer 3150 KVA capacity including brass bush rod/spindle with nuts & wahers complete all as specified & directed by Engineer-in-charge.10.00Each
5Disconnecting transformer from load of any make,any size and any capacity, draining out transformer oil and regular filtration at location in position at site (on pole / platform) filtration upto required dielectric strength 45-50 KV with the help and drying plant by mechanical machines of suitable capacity to achive including testing of dielectric strength all directed by Engineer-in-Charge.6300.00Ltr
27th Jun, 2026