Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 5009959 |
|---|---|
| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Repair And Maint Of 33 Kv Sub Stn And Connected Works At Jorhat Mil Stn |
| Last Date For Submission | 24th Aug, 2026 |
| Opening Date | 26 Aug, 2026 |
| Document Cost | 1000.00 |
|---|---|
| EMD | 115000.00 |
| Estimated Cost | 6000000.00 |
| City | Jorhat |
|---|---|
| State | Assam |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Specific Note: (a) Work shall be executed by the authorised service mechanic/Engineer high skilled as approved by AGE/GE. after satisfacterily completion of servicing of HT Equipments, if any fault occurs upto completion of contract peried should be attended by concerned rep within stripulated time frame without any failure , quoted rates is deemed to be included all such charges. (b) If any HT Equipment and connected items become breakdown, the contractor shall loacate the problem/fault at site within 12 hours on intimation by JE/Engineer-In-Charge and ensure that the fault and rectified within 48 Hours , failing which an amount of Rs 200 /- per hour will be recovered as penal recovery from any payment due to contractor after expiry of 48 hours.) | ||
| 2 | M & L Testing, servicing and commissioning of 11 KV VCB and removing of breaker from existig HT panel and servicing to include cleaning, greasing,corbon removing with CRC/Jelly,Busbar cleaning,removing of sulphonification at Teminals/ busbars and checking the CT,PT working condition,fixing of insulated materials for Busbar and carried out calibration fro desired values (TMS, earth relay timing etc),complete testing and commissioning of 11 KV breaker capacity (As per existing Make / Model) (400 to 800 amp) for 11 KV VCB with panel Installed at different locations for proper functioning of the Installations complete all as specified and directed.( Each VCB will be servcied in one time in entire contract period.) Note:- (a) Visual Inspection (b) Checking of funtional locks, interlocks, signaling devices and auxiliary devices. (c) Checking of suitablility and correct operations of protections, control instruments and electrical connection of the circuit breaker operating mechanism. (d) Checking of Tripping Mechanism operation. (e) checking of Charging Limit Switch Operation. | 15.00 | Each Job |
| 3 | Note Contd/... (f) Checking with standard voltage on the auxiliary circuit. (g) Checking of with standard voltage at potential transformer. (h) Checking of Breaker ON/OFF operation manually and electrically. (j) Testing of vacuum Bottle integrity. (k) Relay testing. (l) Checking of the insulation resistance of VCB. (m) Verification of wiring. (n) Any spare Part if found unserviceable will be measured & paid separately as supply & fix in repair. | ||
| 4 | M&L for Relay setting/Calibration of relay of HT VCB of 11 KV VCB complete all as specified directed. | 14.00 | Each Job |
| 5 | All as per Item No 2 here in above, but 33/11 KV SF6 Circuit Breaker by opening all connections and checking all gases and same should be refilled. All Gases rate shall be deeemed to be included in this rate only. | 4.00 | EACH |