| 1 | Disconnection of existing APFC panel of any capacity/rating, form all incoming and outgoing electrical connections, checking serviceability of each components viz. capacitors, contactors, relays, MCB's, MCCB's, indicator lights, display meters, PF controller, etc., replacement of burnt out internal wirings with with suitable size FRLSH PVC insulated multistranded copper conductor wires, replacement of defective lugs, thimbles etc., replacement of defective parts, through cleaning of panel both internally and externally, re-interconnection of parts including reconnection of all incoming and outgoing electrical connections after repairs, testing and commissioning complete all as specified and as directed. Notes: (i) The work shall be carried out through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by the Engineer-In-Charge. (ii) Spare parts for replacement will be measured and paid seperately. | 20.00 | Each Job |
| 2 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55 C, minimum operating life 150000 hours,rating 5 kVAr, 440 V, complete all as specified and as directed. Make: L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. | 8.00 | Each |
| 3 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55 C, minimum operating life 150000 hours, rating 7.5 kVAr, 440 V complete all as specified and as directed. Make : L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. | 10.00 | Each |
| 4 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55 C, minimum operating life 150000 hours, rating 10 kVAr, 440 V complete all as specified and as directed. Make : L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. | 8.00 | Each |
| 5 | Supply only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In, operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55 C, minimum operating life 150000 hours, rating 12.5 kVAr, 440 V complete all as specified and as directed. Make : L&T, Cat Part No. Box Series: LTBCH or equivalent model of make as specified in Particular Specifications. | 8.00 | Each |