| 1 | Supply, installation, testing and commissioning , LT panel board, 415 Volts, 4 wire, AC 50 Hz, factroy made, outdoor pedestal type, double door type (openable front and back), weather and vermin proof, fabricated of 3.15 mm thick CRCA sheet, confirming to Latest IS 8623(CPRI Approved), powder coated RAL-7032 with seven tank Pre-treatment and outside locking arrangement, two earth terminal, and cable glands for all incoming and outgoing cables including grouting of LT panel 45cm above ground level by providing 90cm long iron angle of size 50x50x6mm welded on all four corners embeded in PCC 1:2:4 using 20mm stone aggregate upto 45cm grouted in ground and 15cm above ground for coping complete all as specified and directed by Engr-in-charge including the following components :-
(a) Four Nos of aluminium bus bars of high conductivity, 3 Nos for phase (RYB) and one No for neutral of current rating 400 Amps mounted on porcelain support.
(b) Incoming : MCCB 250 Amps, four pole 415 volts, adjustable type with breaking capacity 36 KA with spreader links,etc - 01 No.
(c) Outgoing : MCCB 63 Amps, four pole 415 volts, fixed magnetic and thermal type with breaking capacity 10 KA with spreader links,etc - 12 Nos.
(d) Digital type display multi function meter with parameters like Volts, Amps, Frequency, Power factor, etc - 01 No.
(e) LED indication lamp RYB Set of three - 01 No.
| 1.00 | Each |
| 2 | Supply, installation, testing and commissioning , LT panel board, 415 Volts, 4 wire, AC 50 Hz, factroy made, outdoor pedestal type, double door type (openable front and back), weather and vermin proof, fabricated of 3.15 mm thick CRCA sheet, confirming to Latest IS 8623(CPRI Approved), powder coated RAL-7032 with seven tank Pre-treatment and outside locking arrangement, two earth terminal, and cable glands for all incoming and outgoing cables including grouting of LT panel 45cm above ground level by providing 90cm long iron angle of size 50x50x6mm welded on all four corners embeded in PCC 1:2:4 using 20mm stone aggregate upto 45cm grouted in ground and 15cm above ground for coping complete all as specified and directed by Engr-in-charge including the following components :-
(a) Four Nos of aluminum bus bars of high conductivity, 3 Nos for phase (RYB) and one No for neutral of current rating 400 Amps mounted on porcelain support.
(b) Incoming : MCCB 250 Amps, four pole 415 volts, adjustable type with breaking capacity 36 KA with spreader links,etc - 01 No.
(c) Outgoing : MCCB 63 Amps, four pole 415 volts, fixed magnetic and thermal type with breaking capacity 10 KA with spreader links,etc - 12 Nos.
(d) street light timer assembly, three phase, maximum load 12 kw, wired with digital timer switch, contactor TP rating 65 Amp - 01 Set
(e) Digital type display multi function meter with parameters like Volts, Amps, Frequency, Power factor, etc - 01 No.
(f) LED indication lamp RYB Set of three - 01 No. | 1.00 | Each |
| 3 | Supply, installation, testing and commissioning , LT panel board, 415 Volts, 4 wire, AC 50 Hz, factroy made, outdoor pedestal type, double door type (openable front and back), weather and vermin proof, fabricated of 3.15 mm thick CRCA sheet, confirming to Latest IS 8623(CPRI Approved), powder coated RAL-7032 with seven tank Pre-treatment and outside locking arrangement, two earth terminal, and cable glands for all incoming and outgoing cables including grouting of LT panel 45cm above ground level by providing 90cm long iron angle of size 50x50x6mm welded on all four corners embeded in PCC 1:2:4 using 20mm stone aggregate upto 45cm grouted in ground and 15cm above ground for coping complete all as specified and directed by Engr-in-charge including the following components :-
(a) Four Nos of aluminum bus bars of high conductivity, 3 Nos for phase (RYB) and one No for neutral of current rating 400 Amps mounted on porcelain support.
(b) Incoming : MCCB 250 Amps, four pole 415 volts, adjustable type with breaking capacity 36 KA with spreader links,etc - 01 No.
(c) Outgoing : MCCB 63 Amps, four pole 415 volts, fixed magnetic and thermal type with breaking capacity 10 KA with spreader links,etc - 10 Nos.
(d) Digital type display multi function meter with parameters like Volts, Amps, Frequency, Power factor, etc - 01 No.
(e) LED indication lamp RYB Set of three - 01 No. | 1.00 | Each |
| 4 | Supply, installation, testing and commissioning , LT panel board, 415 Volts, 4 wire, AC 50 Hz, factroy made, outdoor pedestal type, double door type (openable front and back), weather and vermin proof, fabricated of 3.15 mm thick CRCA sheet, confirming to Latest IS 8623(CPRI Approved), powder coated RAL-7032 with seven tank Pre-treatment and outside locking arrangement, two earth terminal, and cable glands for all incoming and outgoing cables including grouting of LT panel 45cm above ground level by providing 90cm long iron angle of size 50x50x6mm welded on all four corners embeded in PCC 1:2:4 using 20mm stone aggregate upto 45cm grouted in ground and 15cm above ground for coping complete all as specified and directed by Engr-in-charge including the following components :-
(a) Four Nos of aluminum bus bars of high conductivity, 3 Nos for phase (RYB) and one No for neutral of current rating 250 Amps mounted on porcelain support.
(b) Incoming : MCCB 200 Amps, four pole 415 volts, adjustable type with breaking capacity 36 KA with spreader links,etc - 01 No.
(c) Outgoing : MCCB 63 Amps, four pole 415 volts, fixed magnetic and thermal type with breaking capacity 10 KA with spreader links,etc - 5 Nos.
(d) Outgoing : MCB 40 Amps, four pole 415 volts, with breaking capacity 10 KA - 4 Nos.
(e) Digital type display multi function meter with parameters like Volts, Amps, Frequency, Power factor, etc - 01 No.
(f) LED indication lamp RYB Set of three - 01 No. | 1.00 | Each |
| 5 | Supply, installation, testing and commissioning , LT panel board, 415 Volts, 4 wire, AC 50 Hz, factroy made, outdoor pedestal type, double door type (openable front and back), weather and vermin proof, fabricated of 3.15 mm thick CRCA sheet, confirming to Latest IS 8623(CPRI Approved), powder coated RAL-7032 with seven tank Pre-treatment and outside locking arrangement, two earth terminal, and cable glands for all incoming and outgoing cables including grouting of LT panel 45cm above ground level by providing 90cm long iron angle of size 50x50x6mm welded on all four corners embeded in PCC 1:2:4 using 20mm stone aggregate upto 45cm grouted in ground and 15cm above ground for coping complete all as specified and directed by Engr-in-charge including the following components :- (SV Sub Station)
(a) Four Nos of aluminum bus bars of high conductivity, 3 Nos for phase (RYB) and one No for neutral of current rating 250 Amps mounted on porcelain support.
(b) Incoming : MCCB 160 Amps, four pole 415 volts, adjustable thermal and fixed magnetic type with breaking capacity 25 KA with spreader links,etc - 01 No.
(c) Outgoing : MCCB 63 Amps, four pole 415 volts, fixed magnetic and thermal type with breaking capacity 10 KA with spreader links,etc - 4 Nos.
(d) Digital type display multi function meter with parameters like Volts, Amps, Frequency, Power factor, etc - 01 No.
(e) LED indication lamp RYB Set of three - 01 No. | 1.00 | Each |