| Tender ID | 4352954 |
|---|---|
| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Special Repair/replacement Of Lt Panels With Acbs/mccbs And Apfc Panels And Allied Works At Main Power House And Tech Area Sub Stn And Provn Of Pipeline And Water Tap For Maintenance Of Earthing Infrastructure At Various Placesat Af Station Kalaikund |
| Last Date For Submission | 24th Jun, 2026 |
| Opening Date | 25 Jun, 2026 |
| Document Cost | 1000.00 |
|---|---|
| EMD | 197500.00 |
| Estimated Cost | 12242750.00 |
| City | Kalaikunda |
|---|---|
| State | West Bengal |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of self supported Indoor type totally enclosed panel board of size not less than 9m X 1.2m X 0.9m or suitable size recommeded by OEM, compartmental design, dust and vermin proof, suitable for 3 phase, 4 wire 415 volt, made out of 2mm thick CRCA sheet with built upon rigid frame work, cubical type with angle iron of size 50X50X6mm, duly powder coated, IP 54 as per IS 13947 protection, complete with air circuit breaker, aluminium bus bar 2400 Amp, fault rating 50KA/Sec, having front and rear hinged door with neoprene rubber gasket including danger notice plate, earthing termination points including continous earthing strip alongwith panel, bottom detachable gland plate with holes for incoming and outgoing cables and control circuit diagram with colour code complete with following accessories:- | 1.00 | Set of Panel |
| 2 | (a) Incoming : Air Circuit Breaker,1600A 4P 50KA EDO LSIG Realease, 50 Deg Celcious (ambient temperature) without deration, Short Circuit Breaking Capacity (Icu=Ics=Icw) of 50kA for 1 sec ,100% Neutral , with inbuilt ZSI / Pre Trip Alarm as standard , inbuilt Copper Terminal Adaptor with flexibility of orientation from horizontal to vertical at site upto 4000A With sufficient overlap area for aluminum Bus bar termination, positive interlocking feature while rack in / rack out for correct racking positioning and Position acknowledgement for each position while racking operation, having extended terminal and rotary with breaker ON, OFF, Trip indication, Digital Ampere Meter, Digital Volt meter, selector swithces including suitable CT complete all as specified and directed - 02 Nos. (Make : Hager/Schneider/Seimens) | ||
| 3 | (b) Buscoupler : Air Circuit Breaker,1600A 4P 50KA EDO LSIG Realease, 50 Deg Celcious (ambient temperature) without deration, Short Circuit Breaking Capacity (Icu=Ics=Icw) of 50kA for 1 sec ,100% Neutral , with inbuilt ZSI / Pre Trip Alarm as standard , inbuilt Copper Terminal Adaptor with flexibility of orientation from horizontal to vertical at site upto 4000A With sufficient overlap area for aluminum Bus bar termination, positive interlocking feature while rack in / rack out for correct racking positioning and Position acknowledgement for each position while racking operation complete all as specified and directed - 01 No. (Make : Hager/Schneider/Seimens) | ||
| 4 | (c) Outgoing : Air Circuit Breaker, 630A 4P 50KA EDO LSIG Realease, 50 Deg Celcious (ambient temperature) without deration, Short Circuit Breaking Capacity (Icu=Ics=Icw) of 50kA for 1 sec ,100% Neutral , with inbuilt ZSI / Pre Trip Alarm as standard, inbuilt Copper Terminal Adaptor with flexibility of orientation from horizontal to vertical at site upto 4000A With sufficient overlap area for aluminium Bus bar termination, positive interlocking feature while rack in / rack out for correct racking positioning and Position acknowledgement for each position while racking operation complete all as specified and directed - 12 Nos. (Make : Hager/Schneider/Seimens) | ||
| 5 | (d) ACB panel Bay : Each ACB panel bay shall be equipped with following and cost of the same shall be deemed to be included in quoted rate:- (i) Multifunction Meter: Each bay will display current/voltage/KW/KVA/KVAR/Pf/Hz. (ii) Local/remote switch : Panel needs to be equipped with local/remote with wiring of remote upto terminal block. (iii) Indication : Green (ON) & Red (OFF) indication on each ACB panel console. (iv) Extended cable bus bar: Suitable capacity of aluminium busbars as per I/C & O/G ACB capacity from breaker to O/G cables end termination for accommodate all cables. (v) Suitable copper control cable wiring with proper routed and ducted to each panels. |