Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 3919947 |
|---|---|
| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Repair / Replacement / Maintenance Of External Lt Distribution Equipments And Allied Works At Mil Stn Kapurthala Under Ge Kapurthala. |
| Last Date For Submission | 23rd Apr, 2026 |
| Opening Date | 25 Apr, 2026 |
| Document Cost | 500.00 |
|---|---|
| EMD | 98000.00 |
| Estimated Cost | 4900000.00 |
| City | Kapurthala |
|---|---|
| State | Punjab |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Taking down existing LT panel by disconnecting all incoming and outgoing cables, earthing connection, dismantling PCC and making good the disturbed surface all as directed | 8.00 | Each |
| 2 | Supply, install, testing and commissioning of LT Distribution Panel (CPRI) cubicle type IP-65 , Outdoor type confirming to IS-61439 factory fabricated prewired made out of 3.15 mm thick CRCA sheet outer & 2 mm thick CRCA sheet inner of suitable size to accommodate all accessories/ fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB ad TPN bus bars and outgoing feeders. The TPN bus bars shall be insulated with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision of termination of incoming and outgoing cables. All extension links/ interconnections shall be colour coated sleeves. The cubicle shall have frame work at bottom of MS channel MC 100 fixed to the top of platform. The plateform of LT Panel shall be pedestal type of suitable width and 600 mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class 'B') work duly plastered in CM 1:3 and PCC copping (1:2:4) not less than 50 mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-Charge. A detachable gland plate of thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY structure after seven tank phosphate treatment front & back opening type and fixing 2 Nos danger notice plan with letter figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter with min 3 hinges on each door and shall have louvers and air vent gasket for natural flow of air Neoprene Adhesive type gasket shall be used to make panel vermin proof and comprising of the following | ||
| 3 | Incoming : (i) MCCB 4P 400 Amps, 36 KA 415 Volts (Thermal and magnatic release adjustable range from 70% to 100% ) - 01 No (ii) TPN Aluminium bus bar of capacity min 1.5 times of IC MCCB -01 No's Outgoing : (i) MCCB FP 160 Amps 16 KA 415 Volts (Thermal and magnatic release, adjustable range 70% to 100%) - 03 N (ii) MCB TPN, 63 Amps, 16 KA 415 Volts.- 02 No's (iii) Digital type Digital Timer switch suitable for 3 phase, 415 volts AC supply for street light feeder programmable 1 min, with backup for 6 years, 28 memory locations, current capacity 10 Amps weekly program with 1 changeover | 2.00 | Each |
| 4 | Incoming : (i) MCCB 4P 250 Amps, 36 KA 415 Volts (Thermal and magnatic release adjustable range from 70% to 100% ) - 01 No (ii) TPN Aluminium bus bar of capacity min 1.5 times of IC MCCB -01 No's Outgoing : (i) MCCB FP 100 Amps 16 KA 415 Volts (Thermal and magnatic release, adjustable range 70% to 100%) - 02 N (ii) MCB TPN, 63 Amps, 16 KA 415 Volts.- 02 No's (iii) Digital type Digital Timer switch suitable for 3 phase, 415 volts AC supply for street light feeder programmable 1 min, with backup for 6 years, 28 memory locations, current capacity 10 Amps weekly program with 1 changeover | 2.00 | Each |
| 5 | Incoming : (i) MCCB TPN 160 Amps, 36 KA 415 Volts (Thermal and magnatic release, adjustable range 70% to 100%) - 01 No's (ii) TPN Aluminium bus bar of capacity min 1.5 times of IC MCCB -01 No's Outgoing : (i) MCCB 4 pole 100 Amps 25 KA 415 Volts - 03 No' (ii) MCCB 4 pole 63 Amps 25 KA, 415 Volts - 02 No's (b) Combined Voltmeter & Ammeter 0 to 500 Amps digital type with built in selector switch CTS of suitable ratio (Set of Three) | 4.00 | Each |
18 Days Left