Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 4978658 |
|---|---|
| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Provn Of Transformer To Meet Power Requirements For Installation Of Fast Charger At Group Mt Adm Bn Beg And Centre Khadki Under Ge (central) Khadki |
| Last Date For Submission | 15th Aug, 2026 |
| Opening Date | 18 Aug, 2026 |
| Document Cost | 500.00 |
|---|---|
| EMD | 45954.00 |
| Estimated Cost | 2297700.00 |
| City | Khadki |
|---|---|
| State | Maharashtra |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Supply & install, testing and commissioning step down transformer, out door type and conforming to IS 1180:2014, level -2 plnthe mounted, HT 11 KV, 3 phase 433 volts, 4 wire, 50 Hz delta/star connected, vector group DYN - 11 double copper wound, ONAN, manul type off load tap changing facility on HT side to vary secondary voltage from minimum 7.5% to plus7.5% in steps of 2.5 % continuous rating of capacity 315 KVA including bushing on HT end cable box on LT side. the transformer shall be complete with all standard fittings and accessories, gauges, first fill of btransformer oil IS 335 ISI marked filtered & dehydrated oil etc, complete all as specified and as directed by Engineer - in - Charge. and comprision of the following accessories :- | 1 | Each |
| 2 | (a) primary HV side suitable for OH Coductor(consisting of 3 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nuts and washer. (b) one cable box on secondery (LV) side consisting of 4Nos porcelain busing with GM bushing roads complete with GH nuts and washer with one Nos cable bland suitable for reception of out going LT armoured cables of suitable size. (C ) oil conservator tank with filter type, drain valve and oil level gauge (d) dehydrating breather with first fill of dehydhedratig Agent. (e) thermometer pocket on tank cover (f) one Nos 100mm dia dial type thermometer vapour pressure type having range 0- 120 degree centrigrade with temp reading pointer, max temp indicato and reseting devices (g) rating plate with terminal markings. (h) two earthing terminasl of tank/tanks cover to facilitade fixing of 32x6m GI earthing strip (j) oil level gauge. (k) oil drain and filter valves.(I) oil filter hole with cap/plug with connections complete. (M) lifting lugs. (n) air relief valve plug (o) Four plan soilid cast steel detacheble rollers. (p) first fill of fresh oil confirming to relvant IS and tested up to 50 kV dielectric strength upto top of core (q ) Extra bushing for neutal outside the LT cable box for providing independent earthing for neutral.(r ) provision of 2 Nos danger boards 250x200mm size made of 1.6mm thick MS plate, vitreous enameled white, with letters, figures of voltage and conventional skull and bones in signal red colour, one at HT side and other on LT side. | ||
| 3 | M&L for LT Panel out door type with 3.15 mm thick MS sheet factory made and angle iron of size 50 x 50 x 5 mm angle iron frame, weather proof ventilated with locking arrangement with flollowing accessories complete all as specified and as directed by Engineer - in - Charge. :- (at GP MT ) | 1 | Job |
| 4 | (a) MCCB 4 Pole 400 Amps 36 KA - 1 no.(incoming) | ||
| 5 | (b)MCCB 4 Pole 350 Amps 36 KA 415 volts - 01 no. (outgoing) |