Complete Tender Details

Empowering Indian businesses in the procurement ecosystem since 2012

Tendering Authority: Public Works Department
Tender ID3818918
Organisation NamePublic Works Department
Tender BriefCorrigendum : Upgradation And Modernization Of Electric Power System Of Snm Hospital Leh.
Last Date For Submission20th Apr, 2026
Opening Date21 Apr, 2026
Cost
Document Cost4000.00
EMD926040.00
Estimated Cost39239000.00
Location
CityLEH
StateJammu and Kashmir

Register to see full details

BOQ Items
#ItemQtyUnits
1LT Panel-1 LT Panel Enclosure type tested Supply, installation, testing and commissioning of Form-4 Type 6 LT Panel-1, fabricated from type-tested CRCA sheet steel (2.0 mm outer and 1.6 mm inner), epoxy-polyester powder coated, IP54 rated, mounted on a 75 75 6 mm MS base frame. The panel shall include DMC/SMC supports for Aluminum busbars, aluminum gland plates, stainless steel hardware, segregated functional compartments, ventilation louvers with filters, and galvanized internal structural supports, complete as per relevant IS/IEC standards. The panel shall be equipped with the following: Incomer: - one 4000A ACB (LSIG, EDO type) with Icu/Ics = 100%, 50 kA as incomer; Outgoing: - one 2000A ACB (LSIG) microprocessor-based with Icu/Ics = 100%; one 1250A ACB (LSIG) microprocessor type; one 400A adjustable MCCB; six 250A adjustable MCCBs; and five spare 2-pole breakers. The panel shall include 4500A rated copper busbars, all interconnections and accessories, and complete testing and commissioning. Refer to SLD and Project Specification for full details. Approved Make: - ABB/Siemens/Schneider/L&T1.00JOB
2LT Panel-2 Sub-main Feeder Pillar (external) Supply, installation, testing and commissioning of an outdoor-type Main Feeder Pillar, fabricated from 1.6 mm CRCA sheet steel with epoxy-polyester powder coating, IP65 protection, and equipped with copper busbars, required MCCB/MCB/ACB protections as per the single-line diagram. The feeder pillar shall provide overload, short-circuit and earth-fault protection and shall include all associated works such as foundation, earthing, cabling, termination, site restoration and testing in accordance with IEC standards. The feeder pillar shall be fitted with the following equipment: Incomer: - one 1000A ACB (LSIG) microprocessor-based with Icu/Ics = 100%; Outgoing: - ten 100A 4-pole adjustable MCCBs; two 63A double-pole MCBs; and two 32A double-pole MCBs, all required interconnection accessories; and complete testing and commissioning. Refer to SLD and Project Specification for full details. Approved Make: - ABB/Siemens/Schneider/L&T1.00Job
3Main Feeder Pillar (external) Supply, installation, testing and commissioning of an outdoor-type Main Feeder Pillar, fabricated from 1.6 mm CRCA sheet steel with epoxy-polyester powder coating, IP65 protection, and equipped with copper busbars, required MCCB/MCB/ACB protections as per the single-line di agram. The feeder pillar shall provide overload, short-circuit and earth-fault protection and shall include all associated works such as foundation, earthing, cabling, termination, site restoration and testing in accordance with IEC standards. The feeder pillar shall be fitted with the following equipment: Incomer: - one 1000A ACB (LSIG) microprocessor-based with Icu/Ics = 100%; Outgoing: - ten 100A 4-pole adjustable MCCBs; two 63A double-pole MCBs; and two 32A double-pole MCBs, all required interconnection accessories; and complete testing and commissioning. Refer to SLD and Project Specification for full details. Approved Make: - ABB/Siemens/Schneider/L&T1.00JOB
4Sub-main Feeder Pillar (external) Supply, installation, testing and commissioning of an outdoor-type Sub Main Feeder Pillar, fabricated from 1.6 mm CRCA sheet steel, epoxy-polyester powder coated, IP65 rated, equipped with copper busbars and MCCB/MCB feeders as per the approved single-line diagram. The feeder pillar shall include protection relays, complete foundation work, earthing, cabling and terminations, and all testing in accordance with relevant IEC standards. The feeder pillar shall be provided with following: - Incomer: - one 100A 4-pole adjustable MCCB Outgoing, Two 63A 4-pole adjustable MCCBs, Tw0 40A double-pole MCBs, three 32A double-pole MCBs, supplied, installed and commissioned complete in all respects. Refer to SLD and Project Specification for full details. Approved Make: - ABB/Siemens/Schneider/L&T10.00JOB
5Quarter Feeder Pillar (external) Quarter Feeder Pillar, Supply, installation, testing and commissioning of an outdoor-type Quarter Feeder Pillar, fabricated from 1.6 mm CRCA sheet steel, epoxy-polyester powder coated, IP65 rated, and equipped with copper busbars and MCCB/MCB outgoing feeders as per the approved SLD. The feeder pillar shall include suitable protection relays, civil foundation, cable terminations, earthing, and all testing as per relevant IS/IEC standards. The feeder pillar shall be provided with following Incomer: - one 200A 4-pole MCCB as incomer, Outgoing, two 100A 4-pole adjustable MCCBs, two 40A double-pole MCBs, three 32A double-pole MCBs, supplied, installed and commissioned complete in all respects. Refer to SLD and Project Specification for full details. Approved Make: - ABB/Siemens/Schneider/L&T1.00JOB
20th Apr, 2026

8 Days Left

WhatsApp