Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 4642770 |
|---|---|
| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Upgradation Of Existing Transformer From 250 Kva To 400 Kva For Corps Engr Signal Regt Under Age E/m-ii Of Ge 865 Ews, Leh |
| Last Date For Submission | 14th Jul, 2026 |
| Opening Date | 21 Jul, 2026 |
| Document Cost | 500.00 |
|---|---|
| EMD | 59000.00 |
| Estimated Cost | 2950000.00 |
| City | Leh Ladakh |
|---|---|
| State | Jammu and Kashmir |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Disconnection of Transformer connection 250 KVA from HT and LT side carefully after taking proper safety measures and shifting the same in MES store yard with proper T&P and vehicle, complete all as specified and/or as directed by Engr-in-Charge. | 1.00 | Job |
| 2 | Supply, installation, testing and commissioning of step down Transformer 11/0.415 KV capacity 400 KVA level III, IS-1180 Part-I outdoor type copper wound 3 phase 4 wire, 50 cycle per second, oil immersed naturally cooled external cooling tube core type Delta connection on primary side (HV side) and star connection on secondary side (LV side) having typing 0, + 2.5%, + 5%, + 7.5% to charged by means of hand operated, off load/ tap charging gear including first filling of new transformer oil of dielectric strength not less than 60 KV with standard fitting with such as two earthing terminals for body and one additional for neutral brought out in bushing, oil level gauge indicator for level minimum and maximum, lifting lugs, rating and terminal plate, plain breather device to prevent ingress of rain water and inserts, drain cum sampling value 20 mm bore steel with plug, dial type thermo meter, oil filling hole 32 mm threaded with plug. The transformer shall be powder coated for water/ dust and vermin proof. Note- (1) Transformer oil shall be confirming to requirement of IS 335-1983 specification for new insulating oil for transformer. (2) Equipment shall be suitable to operate at 3500 Mtr above MSL at temperature variation between (-) 25 degree centigrade to (+) 35 degree centigrade, complete all as specified and/or as directed by Engr-in-Charge. | 1.00 | Each Job |
| 3 | S&F HT 11 KV outdoor type gang operated air break switch suitable for horizontal or verticle mounting type complete with 9 insulators upto 200 Amps complete including taking down existing old unserviceable air break switch, complete all as specified and/or as directed by Engr-in-Charge. | 1.00 | Each |
| 4 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, complete all as specified and/or as directed by the Engr-in-Charge. | 2.00 | Each |
| 5 | Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth; for laying of cable in trenches/foundation of pole and stay etc and getting out in soft/loose soil complete all as specified. | 20.25 | Cum |
6 Days Left