| 1 | Solar Power Plant of capacity not less than 38KW
Design, Supply, installation testing and commissioning of solar PV modules of 545Wp of type Mono Perc Half Cut (Mono crystalline) - Minimum 545 Wp each panel Solar Mono Perc144 Cells Module, with module efficiency, 21 % at Standard test conditions with anti reflective coating and anti dust coating confirming to IEC 61215 and IEC 61730 complete including AC DB (with NVR, contactor) & DC DB electrical connection and mounting on GI structure frame all as specified and directed and the following items/equipments are included in rate quoted. Make like TATA /ADANI/WARREE/VIKRAM/MAHINDRA Equivalent make from ALMM, List I of MNRE With solar cells manufactured in INDIA.
Location 1. P-169 | 38.00 | Per KW |
| 2 | Supply, installation & Erection of suitable height as directed by engineer in charge module mounting structure with required accessories for panel mounting [Material: Hot-dip galvanized mild steel (minimum 80 m zinc coating)] suitable for 38KW roof top solar power plant . Column s And Rafters with digging, cementing and Panel laying. (STADD PRO -180KMPH WIND), structure standard for solar panels. Structure shall be mounted using RCC/PCC blocks.MS mounting structures may be used for mounting the modules/ panels/arrays. Each structure should have angle of inclination asper the site conditions to take maximum insolation. Including structure with suitable ladder & walkway and including water pipelines, fittings, jets,valves & pump of suitable capacity with electric cableand connection complete for cleaning of solar panels with accessories. | | |
| 3 | Supply, installation, testing and commissioning of Grid Tied String Inverter suitable for output capacity of solar power plants, 415V AC, 50Hz, respectively at given load condition),IP 68 out door wall mountaing, with efficiency not less than 98% confirming to IEC 600682-2/vde standards with multifunctional LED indications with alarm and complying the following:-
(1) Operating frequency/ range- 50 Hz (49 to 51 Hz), Grid Frequency Synchronization range 1 Hz or more (shall also compatible for Synchronization with DG Set) Waveform- Sine Wave Harmonics AC side total.
(2) Ripple DC voltage ripple content shall not be more than1%
(3) Harmonic current distortion(<3%)
(4) The benchmarking efficiency criteria for the Grid tied ( central/string) inverter
At nominal voltage and full load is >95% For load >25% is >94%.
(5) No load losses should not be more than 5%.
Power Factor > 0.9 complete all as specified and directed by the engineer- in charge.
(6) It shall have MPPT conditional & protection system and fan cooling ventilators
complete all as specified and directed by the engineer- in- charge.
(7) Inverter should have internal protection arrangements against any sustainable
fault in feeder line and against the lightning on feeder.
(8) Inverter generated harmonics, flicker, DC injection limits, voltage, frequency
range and anti-islanding measures should follow latest guide lins/ IEC/BIS codes. | | |
| 4 | S&F Outdoor type IP 65, powder coated, 3.15 mm thickness, with stand of minimum height 2 feet, 1 In 1 Out LT Panel configuration with 160A/100A/ 80A/63A/32A MCCB, AC SPD Type 2 complete, minimum size of enclosure shall be 700 mm x 600 mm x 300 mm along with 4 pole MCCB 160/100/80/63/32 Amps, AC Surge Protection Device-3 phase of 40 kA (as per IEC 60364-5-53), 3 Indication Lamp- R, Y, B with multi-functional meter 3 phase, 415 Volt (Voltage , Current, Power and Energy unit measurement (KWH)), including Copper Busbar including connecting lugs and Double compression glands etc complete as specified and directed.
Make: Switchgear: Siemens, L&T, Legrand, Schneider, SPD: Citel/ Phoenix/ OBO.
Note: -
1. Rate quoted is inclusive of integration & synchronization with existing three phase LT panel supply source.
2.LT panel configuration shall be provided by the contractor as per requirement/designs of solar power plant output capacity). | | |
| 5 | DCDB, ACDB & three phase bidirection energy meter as per description mentioned below:-
(a) Supply, installation connection & testing of AC DB shall be metal clad, totally enclosed, rigid,wall mounted, air ventelator, cubical type suitable for operation on three phase, 415 volts, 50 Hz, 38 KW with type 2 SPD NVR & contactor having provision of incoming & outgoing armoured cable) The panels shall be designed for minimum expected ambient temperature of 45 degree Celsius, 80 percent humidity and dusty weather. All indoor panels will have protection of IP54 or better. All outdoor panels will have protection of IP65 or better. All the 415 volts devices / equipment like bus support insulators, circuit breakers, SPDs, VTs etc., mounted inside the switchgear shall be suitable for continuous operation and satisfactory performance. 1 Nos
(b) Supply, installation connection & testing of DC DB, IP65 Panel shall be metal clad, totally enclosed, rigid, wall mounted, air ventelator, with suitable current rating, 1000 Volts string fuses, DC MCB of 80 Amp, 1000 Volts & DC SPD 1000 Volts as per DC input rating of invertor. 1 Nos.
(c) S & F FRP (Hensel or equivalent make)/PP/ABS with dust, water and vermin proof. provided with proper locking arrangements. Series / Array Junction Box (SJB/AJB) (whichever is required): All the arrays of the modules shall be connected to DC DB. AJB shall have terminals of bus-bar arrangement of appropriate size. Male & Female pair of MC4 connectors compatible with 4sqmm 2 DC solar cable. 1 Nos
| | |