Complete Tender Details

Empowering Indian businesses in the procurement ecosystem since 2012

Tendering Authority: Bharat Sanchar Nigam Limited
Tender ID4464311
Organisation NameBharat Sanchar Nigam Limited
Tender BriefRepairing And Servicing Of 11kv Substation Including Ht Panel,2x500kva 11/0.43 Kv Transformer And Distribution Panel At Cls Sri Vijaya Puram
Last Date For Submission10th Jun, 2026
Opening Date11 Jun, 2026
Cost
Document Cost0.00
EMD11364.00
Estimated Cost568177.00
Location
CityMulti city
StateMulti State

Register to see full details

BOQ Items
#ItemQtyUnits
1Servicing of indoor type HT Panel( 1 I/C + 2 O/G) by authorised person by disconnecting HT supply and drawing out VCB trolley from panel, removing all dust particles from busber and cable termination chamber using air blower & Vacumm machine, cleaning of all male/ female bushing, busbars contacts point, terminals etc. Tightening of all contact terminals and joints of all busbars, CT and PT etc, applying petroleum jelly, complete as required.1Job
2Servicing of 630 Amp HT VCB by authorised person, removing all dust particles from busbar and termination using air blower, vacumm machine, cleaning of all male/ female bushing busbars contacts point, terminals etc. Tightening of all contact terminals and joints of all busbars, greasing of all moving parts etc. complete all as specified and as directed.3Job
3Testing of HT panel and HT VCBs ( following testing to be perform and submit a test report). a) Insulation resistance testing of HT busbars, CTs, PTs and VCBs b) Contact resistance measurement of VCB main contact c) Relay functional testing and setting of over current and earth fault relay d) Functional testing of VCB f) CT & PT testing.1Job
4Servicing of 500 KVA dry type step down indoor transformer 11/ 0.433 KV by disconnecting HT/ LT terminals, cleaning of HT and LT bushings to remove dust particles/ dirt etc., cleaning the core and winding with compressed air and suitable cleaning agents, tightening/ checking of all nut bolts in conducting and non conducting parts, checking of off load taps of HT coils etc, replcing of required spares, as required and directed by engineer in charge.2Job
5Testing of 500 KVA dry type step down indoor transformer 11/ 0.433 KV ( following testing to be perform and submit a test report). a) Insulation resistance testing of HT and LT coil. b) Winding resistance measurement. c) Transformer turns ratio test. d) Megnetic balance test. f) Functional testing of protections2Job
10th Jun, 2026

8 Days Left

WhatsApp