Complete Tender Details

Empowering Indian businesses in the procurement ecosystem since 2012

Tendering Authority: Military Engineer Services
Tender ID5026094
Organisation NameMilitary Engineer Services
Tender BriefAutomation Of Water Supply Distribution Network To Jhelum Building And Left Over Portion Of Chenab Building And Its Connected Pump House At Nofra Area Under Ge(nw) Navy Nagar, Colaba, Mumbai
Last Date For Submission10th Aug, 2026
Opening Date12 Aug, 2026
Cost
Document Cost500.00
EMD62340.00
Estimated Cost3117000.00
Location
CityMumbai
StateMaharashtra

Register to see full details

BOQ Items
#ItemQtyUnits
1Supply and fixing, Installation Testing & Commissioning of Indoor type Programmable Logic Controller based Valve Automation and communication Panel suitable for control and/or monitoring of 03 Nos. Pumps, 03 Nos Pressure Transmitter, 03 Nos. Priming Solenoid Valves, 03 Nos. Air release Solenoid Valves, 8 Nos motorized valves (+02 Spare) and 04 Nos. magnetic sensors PrimingTanks-01(2 Levels), energy meters and 01 Nos Ultrasonic level sensor, . The panel should be of suitable size fabricated from 2.0 mm thick CRCA sheet and properly powder coated. PLC with following specifications:- (i) Suitable Digital inputs/ outputs, (ii) 4 serial ports supporting open communication protocol, 01 No. Ethernet port, (iii) Programming software based on IEC to facilitate building of custom built function blocks (iv) Expandable up to 192 DI / DOs. (v) 01 No. SMPS of 5 A rating (Make: SCHNEIDER / NHP) (vi) Suitable no. of interposing relays 24 V D.C. coil rating, 4 pole and 2 A contact rating. (Make: OEN / OMRON / IDEC / ALLEN BRADLEY) (vii) Selector Switches as per requirement (Make: SCHNEIDER / ESBEE). (vii) Selector Switches as per requirement (Make: SCHNEIDER / ESBEE). The control logic shall be as directed by the Engineer In Charge for Automatic Operation of Motor Actuated Valve, Supply: 230V, 50 Hz Compatible with OFC based and GPRS communication. Compatible for Wimax Connectivity if required. Mounting: Grouted on floor on angle support /on Wall 1.00Each
2To make the system fully functional. all panels shall be consisting of the following :- (a) Rack mountable Web Smart Switch with 28 ports and POE for CPE hardware and following specifications:- (i) Number of Ports 24 10/100Base-TX Ethernet ports 2, 10/100/ 1000BASE-T 2 Combo 10/100/1000BASE-T/SFP. (ii) Port Standard Supply and fixing functions IEEE 802.3 10BASE-T Ethernet (twisted-pair copper) IEEE 802.3ab 1000BASE-T Gigabit Ethernet (twisted-pair copper) IEEE 802.3x Flow Control IEEE 802.3u 100BASE-TX Fast Ethernet (twisted-pair copper) IEEE 802.3z Gigabit Ethernet (fiber) ANSI/IEEE 802.3 IEEE 802.3z Gigabit Ethernet (fiber) ANSI/IEEE 802.3 Switching Capacity 12.8 Gbps Make : Siemens, Dlink, Ubiquiti, Cisco (b) Hot pluggable 1310 nm multimode/Single mode SFP (mini-GBIC) transceiver, supporting full duplex, Gigabit speeds on multimode/Single mode fiber for distances of up to 550m/550m/10km on 62.5 m/50 m/ 9 m respectively in a metal housing to reduce EMI and to increase durability Make : Dlink, Ubiquiti, Cisco, Siemens, HP (c) Rack Mountable LIU with the following specifications:- (i) Rack Mountable 12 Port Unloaded LIU (ii) Aluminium Base Material (iii) Slim 1 U mounting height (iv) Metal Shelf Aluminium 1.2 mm thick (v) Splice tray Aluminium 0.6mm (vi) Winding Panel Plastic
3(vii) Cable Plug Rubber for minimum 2 cable entries (viii) Adaptor Panel Aluminium 1.5 mm thick (ix) 2 fiber spools built in for 900 um tight buffered fibre storing (x) Capable of storing upto 3 mts of 900 um tight buffered fibre per adaptor Make : Dlink, Ubiquiti, Cisco (d) SC-LC Duplex SM Patch Cord 0.9 mm dia of suitable length (i) Size 0.9mm dia (ii) Insertion Loss <=0.2 db, max 0.3 db (iii) Return Loss PC>=45dB, UPC>=50dB, APC>=60dB (iv) Connector Ferrule Ceramic (v) Apex Offset <50um (vi) Fiber Height +-100nm (vii) End Face Radius of Curvature 7mm<R<25mm (viii) Repeatability <=0.2 dB 1,000 times mating cycles (ix) Working Temp -40deg C to +85 deg C Make : Dlink, Ubiquiti, Cisco
4Seamless Integration of the above PLC Panels into the Existing SCADA System incorporating (a) Development: (i) SCADA Screens for new Updated Panel configuration (ii) Layout for App new Updated Panel configuration (iii) Report Format new Updated Panel configuration (b) On-site development: (i) Modifications in SCADA Screens (ii) Modifications in reporting format (iii) Modifications in App layout
5The quoted cost shall deem to be included the cost of communication for 12 months from the date of completion. Above All automation panel should connected to existing SCADA server and any other leftout devices and accessories require to commissioning should be consider and same should be include in quoted rates and department will not pay extra cost for the same. Note :- Cost for Synchronising of panel in to existing SCADA system is in contractors scope only and no extra payment shall be given to the contractor by the department.
10th Aug, 2026

20 Days Left

WhatsApp