| 2 | Supply, Installation, Testing & Commissioning of Analogue Addressable 100% Hot Redundant (Display, Mother Board, Loop Card, PSU, Battery, Network Card and all other components) with inbuilt Automatic switcher of 2 Loop Fire Alarm Control Panel expandable via plug-in loop driver boards, loop current 500mA maximum per loop, dual flash based microprocessor, supports to connect 20% spare detector in Each loop via fully digital communication protocol, equipped with a white backlit display (600 Character/240x64 pixel resolution/10" Touchscreen) graphical LCD Display with at least 6 lines of information, 400 fire zones (soft zones), fully programmable via alphanumeric keypad or configuration software without using any king of DONGLE/LICENCE/SPECIAL CABLE, dedicated USB and RS-232 serial port for direct or PC connection, 5000 events storage, loop current 500 mA, panel shall be equipped with inbuilt multi-meter for live monitoring of loop current, earth voltage, loop voltage etc., installer's logo application, inbuilt fault-tolerant network card to network with compatible addressable panel(s) and repeater panel(s), capable to connect maximum 200 network nodes on a standard network, features battery charger status and temperature, supports programmable cause / effect on outputs, panel housing meets min IP30 ingress protection classification finished in RAL 7035, The panel shall support more than one OEM protocol to allow user of using other make detector & devices at later stage. (The System cost shall be included of all necessary cards, modules, Panel enclosure, CPU and associated accessories to complete the system design). Approved by: International Independently certified as complying with requirements of BS EN 54 Part 2, 4, and 13. Note: The FACP shall communicate over peer-to-peer communication network complete all as specified and directed by Engineer-in-Charge. | 5.00 | Each |
| 3 | MAIN FIRE ALARM CONTROL PANEL OR NETWORK NODE: 1. Main FACP or network node shall contain a microprocessor based central processing unit (CPU) and power supply. The CPU shall communicate with and control the following types of equipment used to make up the system: intelligent addressable smoke and thermal (heat) detectors, addressable modules, printer and other system control device. 2. In conjunction with intelligent loop control modules and loop expander, the main FACP shall perform the following function: supervise and monitor all intelligent addressable detectors and monitor modules connected to the system for normal, trouble and alarm conditions, supervise all initiating signalling and notification circuits throughout the facility by way of connection to addressable monitor and control modules, detect the activation of any initiating device and the location of the alarm condition, Operate all notification appliances and auxiliary device as programmed complete all as specified and directed by Engineer-in-Charge. | | |
| 5 | DIGITAL VOICE COMMAND CENTRE: 1. The digital voice command centre located with the FACP, shall contain all equipment required for all audio control, emergency telephone system control, signalling and supervisory functions. This shall include speaker zone indication and control, telephone circuit indication and control, digital voice units, microphone and main telephone handset. 2.Function: The voice command centre equipment shall perform the following function: a. operates as supervised multi-channel emergency voice communication system. Operate as a two-way emergency telephone system control centre. b. Audibly and visually annunciate the active or trouble condition of every speaker circuit and emergency telephone circuit. c. Audibly and visually annunciate any trouble condition for digital tone and voice units required for normal operation of the system. d. provides all call emergency paging activities through activation of a single control switch. | | |