Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 3991871 |
|---|---|
| Organisation Name | Maharashtra Industrial Development Corporation |
| Tender Brief | Nardana Indl.area M And R To Wss Providing Erecting Testing Of Ht Rmu Panel At Raw Water Pump House And Replacement Of Sump Incoming Gate And Allied Works At Wtp Second Call |
| Last Date For Submission | 22nd Apr, 2026 |
| Opening Date | 23 Apr, 2026 |
| Document Cost | 8850.00 |
|---|---|
| EMD | 40000.00 |
| Estimated Cost | 3992834.00 |
| City | Nashik |
|---|---|
| State | Maharashtra |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | HT SF6 Load Break Switch /RMU (SW-HTS) Supplying, erecting, testing & commissioning 11kV, 630A, 21kA/3sec, 6 way outdoor, extensible motorised SCADA compatible RMU, internal arc tested consisting of 2 nos. feeder with 2 LBS and 4 nos. feeder with 4 VCB compliant to IEC 62271-100, 200 and 102 as per specification no. SW-HTS/RMU SCADA. | 1 | each |
| 2 | C.C. Foundation Making M-20 cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at size of 1.50 m X 1.50 m X 2 m including excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 12.5m raising lowering high mast). | 1 | each |
| 3 | LT Cables (Aluminum) (CB-LT/AL) Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3 core 185 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL | 460 | Meter |
| 4 | Supply and erecting iron work,, sheet metal work consisting of MS sheets, various sections of iron plates, chequired plates, rode bars, MS pipes etc for RMU panel, board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions of engineers. | 850 | kilogram |
| 5 | Accessories Supplying and erecting 11 kV outdoor type gang operated air break, triple pole switch 200 A capacity with 3 post pin type insulator per phase, mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of "C" class G.I. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp. | 1 | Per Set |
8 Days Left