Complete Tender Details

Empowering Indian businesses in the procurement ecosystem since 2012

Tendering Authority: Military Engineer Services
Tender ID4168609
Organisation NameMilitary Engineer Services
Tender BriefCorrigendum : Repairs/ Replacement Lt Panel, Ug Cables And Connected Items Wellington Station Under Ge Wellington
Last Date For Submission2nd Jun, 2026
Opening Date13 Jun, 2026
Cost
Document Cost500.00
EMD90000.00
Estimated Cost4500000.00
Location
CityNilgiris
StateTamil Nadu

Register to see full details

BOQ Items
#ItemQtyUnits
1Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings and base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement including taking out old unserviceable panel board with accessories such as MCCBs complete with following cables all as specified and directed. (9 Mal lake view sub station & Lake view near High Mast light) (a) INCOMING:- (i) MCCB thermal magnetic release, adjustable over load, 80-100% 4 Pole, 36 KA, 250 Amps 415 Volt - 1 No (b) OUTGOING (i) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 200 Amps 415 Volt - 1 Nos (ii) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 160 Amps 415 Volt - 1 Nos (iii) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 100 Amps 415 Volt - 2 Nos (iv) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 16 KA, 63 Amps 415 Volt - 2 Nos (v) MCCB thermal magnetic release, adjustable over load, 80-100% 3 Pole, 25 KA, 40 Amps 415 Volt - 2 Nos (vi) Astronomical time switch for 24 Hrs setting-1 Nos. (vii) 2 Pole power contactor AC 3 rating 25 Amps AC1 rating 45 Amps MNX 25-2P type-1 Nos. (c) 500 Amps aluminium busbar for phase and 300 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulators in separate compartment - 01 Set (d) Digital multi function panel meter for measuring voltage, Amps and Frequency with suitable CTs and back up protection - 1 Nos (e) LED type Indication lamp 415 Volts Set of three - 1 Set (f) danger notice board of size 200 mm x 150 mm x 1.6 mm thick of mild steel sheet printed with vitreous enabled white paint and letter figure and convention skull and bones of signal red colour and fixed / rivetted with panel -02 Nos Note:- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level. (iii) Outgoing MCCBs shall be fed with solid busbar connectors. (iv) Cables shall be terminated using gun metal /SS glands. 6.00JOB
2MCCB 4 pole, 415V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as specified and directed.3.00EACH
3MCCB 4 pole, 415V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified and directed.5.00EACH
4MCCB 4 pole, 415V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as specified and directed.6.00EACH
5MCCB 4 pole, 415V, Adjustable type, 400 Amps with breaking capacity 36 KA complete all as specified and directed.2.00EACH
2nd Jun, 2026

6 Days Left

WhatsApp