Empowering Indian businesses in the procurement ecosystem since 2012
| Tender ID | 4520430 |
|---|---|
| Organisation Name | Military Engineer Services |
| Tender Brief | Corrigendum : Repair Maintenance Replacement Of Ht Electrical System Of Dib And Dia Zone Under Age Em I Of Ge N Mamun |
| Last Date For Submission | 3rd Jul, 2026 |
| Opening Date | 10 Jul, 2026 |
| Document Cost | 500.00 |
|---|---|
| EMD | 80000.00 |
| Estimated Cost | 4000000.00 |
| City | Pathankot |
|---|---|
| State | Punjab |
| # | Item | Qty | Units |
|---|---|---|---|
| 1 | Dismantling air break switch with all accessories such as insulators with mountings, all current carrying parts,GI pipe etc ON-OFF handle complete set complete all as specified and directed. | 8.00 | Each |
| 2 | Supply, installation, commissioning and testing 11 KV Air break switch, gang operated for current rating upto 200 Amps, triple pole, horizontal type, mechanically operated with accessories such as polymer insulator assembly (Set of 15 insulators), All current carrying parts shall be of non-ferrous metal or alloys and shall be designed to limit sharp points/edges, A set of adjustable arcing horns made from 2 SWG GI wire shall be mounted on each insulator stack of G.O pad-locking arrangement for both ON and OFF positions, operating mechanism worked from ground level, Height of operating handle may vary from 1000 to 1300mm, GI tubing 20mm bore (heavy grade) for connecting operating handle, pad-locking arrangement shall be provided for both ON and OFF positions drop out fuse. All steel parts are applied of two coats of aluminium paint over a coat of primer complete all as specified and directed. | 6.00 | Each |
| 3 | All as per Srl item No 2 here-in-above but gang operated switch for current rating upto 400 Amps complete all as specified and directed. | 2.00 | Each |
| 4 | Taking down transformer any capacity upto 100 KVA after disconnecting all the electric cables and earthing connections from 11/0.433 KV unserviceable transformer from platform/room of capacity upto 100 KVA and shifting to workshop including loading unloading carefully by manual or mechanical means and refixing and testing after repair works complete all as specified and directed. Note: Cost of repair shall be measured and paid under relevant items. | 2.00 | Each Job |
| 5 | All as per Srl item No 4 here-in-above but capacity of transformer above 100KVA and upto 200 KVA complete all as specified and directed. | 3.00 | Each Job |
6 Days Left