Complete Tender Details

Empowering Indian businesses in the procurement ecosystem since 2012

Tendering Authority: Military Engineer Services
Tender ID4124885
Organisation NameMilitary Engineer Services
Tender BriefCorrigendum : Repair And Replacement Of Lt Overhead Distribution System To Underground Cable And Allied Work At Zone A And B Under Age (i) Raiwala
Last Date For Submission23rd May, 2026
Opening Date25 May, 2026
Cost
Document Cost500.00
EMD20000.00
Estimated Cost1000000.00
Location
CityRaiwala
StateUttarakhand

Register to see full details

BOQ Items
#ItemQtyUnits
1Dismantling unserviceable LT panel /Bus bar of any size from the site and removing existing concrete block complete all as specified and directed4Each
2Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board of size 1 .2x1.0x0.8 m , Out door type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm 4 core), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade copper shrouded bus bar of capacity 400 Amp rated fixed on DMC insulators INCOMER : (i) MCCB 250 Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable thermal magnetic release, Ics = 100%=Icu(1 sec) complete including phase spreaderall as specified and directed. 01 Nos. (ii) Multifunction meter = 01 set. (iii) Phase Indication lamps (RYB), LED type - 01 No (set of three).(iv) CT( Current transformer)- Set of 3 Nos Outgoing : (a) (i) MCCB 125 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 02 Nos (ii) MCCB 63 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 01 No (iii)MCCB 40 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 01 No (i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests). (ii) All the electrical switch gear like MCCBs, MCBs should be of same make, (v) Drawing of panel board should be got approved from AGE(I) before fabrication.1Each job
3Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board of size 1 .2x1.0x0.8 m , Out door type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side open able, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm 4 core), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : - (a) Busbarchamber : Electrically grade copper shrouded bus bar of capacity 200 Amp rated fixed on DMC insulators INCOMER : (i) MCCB 125 Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable thermal and magnetic release, Ics = 100%=Icu(1 sec) complete including phase spreaderall as specified and directed. 01 Nos. (ii) Multifunction meter = 01 set. (iii) Phase Indication lamps (RYB), LED type - 01 No (set of three).(iv) CT( Current transformer)- Set of 3 Nos Outgoing : (a) (i) MCCB 63 Amps, 415Volts, 4 pole 50 Hz, 25 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) complete including phase spreader all as specified and directed- 02 Nos (ii) MCB TPN 32 Amps, 415Volts, 4 pole 50 Hz, 10 KA 'C' curve complete including phase spreaderall as specified and directed - 01 No. (i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests). (ii) All the electrical switch gear like MCCBs, MCBs should be of same make, (v) Drawing of panel board should be got approved from AGE(I) before fabrication.1Each job
4Supply and fixing in repair Bus bar chamber of size 0.7x0.7x0.6 m made out of 3.00 mm thickness sheet metal enclousre totaly enclosed outdoor type, vermin proof, powder coated paint, metal clad with porcelain insulator and colour coated tinned copper bus bar 415 volts, 200 Amps rated, 4 pole for connecting UG cable, fixed on ground and required size of steel clamp, screw, bolt, nut, washers for tightend with pole, in outer site the letters shown Danger 440 volts all as specified and directed by Engr-in-Charge. (Note-: The price for foundation is included in quoted rate).2Each
5Taking out unserviceable / serviceable cable /UG cable of any size upto 240 Sqmm carefully from trenches/poles/ducts/LT panels, OH conductors at different locations all as specified and directed by Engr-in-Charge.750RM
23rd May, 2026

6 Days Left

WhatsApp