| 1 | Supply, installation, testing, programming & commissioning of Computer System, i7 Processor, latest generation, 2.93GHz, 4MB Cache with 16 GB RAM, & 1 TB SSD, 2GB 4K Graphics Card, 10/100 Mbps Ethernet card, USB connection & internal modem, Microsoft(R) Windows(R) 10 OS Professional Enterprise or latest, Web server software, 100/1000 Mbps NIC for Network connection and antivirus software as per Specifications. Accessories included 50 Inch UHD 4K LED Screen, Optical Mouse & Key Pad, Windows Licensed software compatible with the above FAS System configuration complete all as specified and directed.
NOTE:
Fire alarm system shall be connected to a computer-based monitoring system with real-time alarm, fault display, event logging, and reporting. Complete supply, installation, configuration, testing, commissioning, and training shall be included in the contractor s quoted rate. | 2.00 | EACH |
| 2 | Supply, Installation, Testing & Commissioning of scaleable & upgradeable software for Fire Alarm System with features like 3D vector dynamic graphics with AutoCAD import of plan with Zoom In & Zoom Out facility, Plant Viewer, Trend Viewer, Object Viewer, Report Viewer, Alarm router. The Web-Based Server software shall permit use of Standard Web- Browsers such as Microsoft Internet Explorer, Netscape Navigator, etc. The software shall be capable of integration third-party systems and should supports latest IP technology (IP V4/V6). The Web based software shall include Client License for remote viewing. The software shall have Online Engineering capability i.e. Zero Downtime for software graphics modification. Software should be capable to integrate BMS, Gas Suppression & VESDA Panels Seamlessly complete all as specified and directed.
Software should comply to OPEN Protocols like:
- BACnet/IP for HVAC Automation / BMS
- SNMP for UPS & Networking Integration
- Modbus/IP for Energy Monitoring
- IEC61850 for Electrical & Power Integration
- ONVIF for CCTV Integration
- OPC for any other Integration.
| 1.00 | EACH |
| 3 | NOTE:
The project comprises multiple buildings, and each building shall be provided with a separate and dedicated 3D graphical representation on the fire alarm computer-based monitoring system. The 3D graphics shall clearly indicate building layout, floors, zones, and locations of all fire alarm devices with real-time fire, fault, and supervisory status. The contractor shall include complete development, configuration, integration, testing, and commissioning of all 3D graphics for each building within the quoted scope, without any additional cost. | | |
| 4 | Supplying, installation, testing and commissioning of UL 864 10th edition UL Listed and FM approved Analog addressable 2 Loop Fire Alarm Control Panel having the total panel capacity of 252 devices. The panel shall be able to give pin point location of all Fire /fault and Isolation conditions of addressable units via the address codes. The panel shall have the capacity of storing upto 10000 events. Further, the panel must be able to automatically switch ON /OFF respective control module whenever any alarm is triggered. The panel should have inbuilt common Alarm, Fault and monitored sounder output. The panel shall have a 2 x4-3/4 Size VGA monochrome LCD display and having maximum 320 (8 x 40) Characters in the display with optional 24 Zones LED indicators. The panel shall have a built in power supply of 170 Watts and battery charger. Battery charger shall be able to charge the system batteries of upto 33AH capacity. The Panel shall have the capacity of connecting additional 31 panels or Network terminals using network card, with redundancy in the network. The panel shall have the capacity of connecting maximum 16 Remote terminals /16 remote displays or combined by using. The panel shall be compatible for IBMS system with open protocol BACnet over IP complete all as specified and directed.
| 4.00 | EACH |
| 5 | NOTE :
All disturbed existing surfaces shall be made good after completion of works. Any damage caused during execution shall be repaired and restored by the contractor at no extra cost. | | |