| 1 | Design, manufacture and Supply of indoor compartmentalized type LT panel 36 kA short circuit breaking capacity panel of suitable size bus bars with SMC/DMC supports made of 2mm CRCA sheet totally enclosed,IP-42,free standing floor/ wall mounting,powder coated painting suitable to operation on 3 phase and neutral,415V,50Hz AC system with bus bars G.I flat Earth strip on both sides, Removeable gland plates at bottom with suitable size of predrilled holes for cabels,cable interconnections,wiring earthing,rotary handles & spreader links to all MCCBs,powder coated painting etc,with following items and installation on suitable channels / elevated concrete foundation as per site requirement/directions of E-I-C.
INCOMER
(a) 200 A, 4P MCCB, Microprocessor based release (lcs = Icu = 36kA) with inbuilt O/L , S/C & E/F protection, shunt trip, auxiliary contacts - 2 Nos
(b) R, Y, B phase indicating LED lamps with 2 amp back up MCB - 2 Set
(c) Digital Mulit functional meter suitable range for 3 phase 4 wire with LED display and selector switch along with MCB of suitable ratings - 02 sets for 3 phase 4 wire with LED display and selector switch and cast resin CT ratio progragmmable and auto ranging along with 3 numbers of class 1.0,15VA suitable range CTs-02 Sets.
(d) ON, OFF, TRIP Indicating LED Lamps With 2 Amp MCB - 2 Set
MANUAL CHANGE OVER SWITCH
One set of four pole 200 Amps, 36 KA capacity
BUSBAR
One set of 400 Amps TPN Aluminium Busbar of 36 KA capacity
OUTGOING
a) 63 A, 4P MCCB with built in Microprocessor based release with adjustable thermal setting (lcs = Icu =36 KA) - 01 Nos.
(b) 100 A, 4P MCCB with built in Microprocessor based release with adjustable thermal setting (lcs = Icu =36 KA) - 03 Nos.
| 1.000 | job |
| 2 | Design, manufacture and supplyof outdoor compartmentalized type feeder pillar 36 kA short circuit breaking capacity panel of suitable size bus bars with SMC/DMC supports made of 2mm CRCA sheet totally enclosed,IP-65,free standing floor/ wall mounting,powder coated painting suitable to the existing space,operation on 3 phase and neutral,415V,50Hz AC system with bus bars G.I flat Earth strip on both sides, Removeable gland plates at bottom with suitable size of predrilled holes for cabels,cable interconnections,wiring earthing,rotary handles & spreader links to all MCCBs,powder coated painting etc,with following items and installation on suitable channels / elevated concrete foundation as per site requirement/directions of E-I-C.
INCOMER
(a) 100 A, 4P MCCB, Microprocessor based release (lcs = Icu = 36kA) with inbuilt O/L , S/C & E/F protection, shunt trip, auxiliary contacts - 2 Nos
(b) R, Y, B phase indicating LED lamps with 2 amp back up MCB - 2 Set
(c) Digital Mulit functional meter suitable range for 3 phase 4 wire with LED display and selector switch along with MCB of suitable ratings - 01 sets for 3 phase 4 wire with LED display and selector switch and cast resin CT ratio progragmmable and auto ranging along with 3 numbers of class 1.0,15VA suitable range CTs-02 Sets.
(d) ON, OFF, TRIP Indicating LED Lamps With 2 Amp MCB - 2 Set
BUSBAR
One set of 200 Amps TPN Aluminium Busbar of 36 KA capacity
OUTGOING .
(a) 32Amps, 4P power contractor with 230 volts 50 HZ contrctor coil connected through 24 hour timer for perimeter lighting - 01 set.
b) 01 no. 6 way horizontal TPN DB consisist of 03 no.10 Amps TPN MCB, 01 no. 6 Amps SPN MCB,
| 7.000 | job |
| 3 | Installation Testing and commissioning of Indoor type LT panel on existing cable trench by provinfing suitable MS channels/Angles including cutting, welding, grinding and painting as per site requirement / directions of E-I-C. | 1.000 | job |
| 4 | installation,testing and commisioning of outdoor type feederpillar by provinfing suitable MS channels/Angles including cutting, welding, grinding and painting / elevated concrete foundation as per site requirement/directions of E-I-C. | 7.000 | job |
| 5 | Supply of following size of XLPE insulated & PVC sheathed, armoured, aluminium conductor under ground cable of 1.1KV grade as per IS 7098:1988 Part-I with upto date amendments complete as required.
2C x 6 Sq.mm | 150.000 | Meter |