| 1 | Installation, Testing & Commissioning of 33kV Outdoor VCB, (VCB will be suuplied by the department),
Scope of Work:- PCC/RCC work to be made as per foundation drawing (LXBXH = 3.0m X 2.2m X 0.6m), Erection of VCB Structure, Shifting of VCB from store to site, incoming & outgoing conductor connection, Control cable ferruling & connection, VCB 33kV testing (Contact Resistance measurement, Breaker Timing Test, Vaccuum Integrity Test) by engaging test kit for final commissioning and trouble free operation. Secondary Relay Testing & Checking its all tripping function with associated breaker. | 1 | No |
| 2 | Installation, Testing & Commissioning of 33kV Outdoor VCB, (VCB will be suuplied by the department),
Scope of Work:- Erection of VCB Structure, Shifting of VCB from store to site, incoming & outgoing conductor connection, Control cable ferruling & connection, VCB 33kV testing (Contact Resistance measurement, Breaker Timing Test, Vaccuum Integrity Test) by engaging test kit for final commissioning and trouble free operation. Secondary Relay Testing & Checking its all tripping function with associated breaker. | 2 | Nos. |
| 3 | Dismantling of old & surveyed off 33kV MOCB.
Scope Of work: Opening incoming & outgoing conductor with pad clamp,Drain of insulation oil from MOCB chamber,marking & disconnection of control wires, dismantling of 3 poles, mechanism ,mechanism box, dismantling of structure ,dismantling of foundation and shifting of all material to stockyard. | 2 | No |
| 4 | Supply, Installation, Testing & Commissioning of new 33kV Outdoor CT, primary, secondary connection of 33kV Current Transformer.
(3 nos= 1set) Scope of Work:- Supply of New one set (3 nos= 1set) of 33kV CT, Structural steel work base for erection of the CT set, incoming & outgoing conductor connection, Secondary terminal wiring & ferruling of CT Junnction box, CT 33 KV testing (Primary Injection, Ratio, Burden, Knee Point Voltage, Accuracy Class, Phase angle error) by engaging test kit for final commissioning. Supply & Erection of CT Termination BOX. | 1 | Set |
| 5 | Installation, Testing & Commissioning of new 33KV Outdoor PT, primary, secondary connection of 33kV Potential Transformer. (PT will be supplied by the department) (3 nos= 1set) Scope of Work:- Shifting of New PT from store to site, Structural steel work base for erection of the PT set, incoming & outgoing conductor connection, Secondary terminal wiring & ferruling of PT Junnction box, PT 33 KV testing (Ratio, IR Test) by engaging test kit for final commissioning. | 1 | Set |