Complete Tender Details

Empowering Indian businesses in the procurement ecosystem since 2012

Tendering Authority: Military Engineer Services
Tender ID4623578
Organisation NameMilitary Engineer Services
Tender BriefCorrigendum : Repair/ Maint Of Vcbs / Rmus Alongwith Allied Services Of Chnc And Northern Part Of Garrison Under Ge (utilities) Udhampur
Last Date For Submission20th Jul, 2026
Opening Date22 Jul, 2026
Cost
Document Cost1000.00
EMD175000.00
Estimated Cost10000000.00
Location
CityUdhampur
StateJammu and Kashmir

Register to see full details

BOQ Items
#ItemQtyUnits
1M & L for carrying out following on site Tests for 33 / 11 KV 3.15 MVA Transformer of any capacity with required / suitable testing equipment by Qualified and Licensed Personal, Recording Test Results and submitted to GE to keep on record duly signed by all concerned complete all as specified and as directed: [a] IR Test [b] PI [c] Magnetic Balance Test [d] Ratio test [e] Di-electric Test of Oil [f] Short Circuit Test [g] Vector Group [h] Winding Resistance [j] All test to be carried out as per applicable IS.3.00Each Job
2All as per item No. 01.00 but for 11 kv/ 0.433 KV transformer 1250 KVA6.00Each Job
3M & L for Repairs / Servicing of 33KV VCB indoor/outdoor type VCB having nominal system voltage 33KV highest system voltage 36KV interrupting capacity, frequency 50Hz, short circuit current 25KA, control circuit voltage 110V DC, of ABB make and comprising of the following complete all as specified and as directed: [a] Cleaning of Vacuum Interrupter Limbs for Dust, Oxidising and Decarbonising with CTC. [b] Repair / Servicing of Spring Loaded Operating Mechanism [c] Repair / Servicing of Spring Charging Motor [d] Checking, repairing & servicing of Gearbox, Auxiliary Switches, Spring, Limit Switch etc. complete [e] Checking & Repairing Electrical and Mechanical Operations [f] Checking & Repairing Remote Closing and Tripping of VCB from 33KV Control Panel. [g] Lubrication all Moving Parts with Petroleum Jelly & cleaning all Bushing Insulators with CTC [h] Tightening of all Mechanical Connections of Mechanism [i] Tightening of all HV and LV Connection of VCB. Note: Spares required for Servicing / Repairing of 36 KV Circuit Breaker shall be measured and separately under respective items of this BoQ at supply only rates. 2.00Each Job
4M & L for Repairs / Servicing of 11KV VCB indoor type with hallow porcelain insulated porcelain clad VCB having nominal system voltage 11KV highest system voltage 36KV interrupting capacity, frequency 50Hz, short circuit current 25KA, control circuit voltage 110V DC, of ABB make and comprising of the following complete all as specified and as directed: [a] Cleaning of Vacuum Interrupter Limbs for Dust, Oxidising and Decarbonising with CTC. [b] Repair / Servicing of Spring Loaded Operating Mechanism [c] Repair / Servicing of Spring Charging Motor [d] Checking, repairing & servicing of Gearbox, Auxiliary Switches, Spring, Limit Switch etc. complete [e] Checking & Repairing Electrical and Mechanical Operations [f] Checking & Repairing Remote Closing and Tripping of VCB from 33KV Control Panel. [g] Lubrication all Moving Parts with Petroleum Jelly & cleaning all Bushing Insulators with CTC [h] Tightening of all Mechanical Connections of Mechanism [i] Tightening of all HV and LV Connection of VCB. Note: Spares required for Servicing / Repairing of 36 KV Circuit Breaker shall be measured and separately under respective items of this BoQ at supply only rates. 8.00Each Job
5Tripping latch Assembly for 33 KV Indoor SF6 Breaker of make ABB as per existing model complete all as specified and as directed.2.00Each
20th Jul, 2026

6 Days Left

WhatsApp