| 1 | Supply, installation, testing & commissioning of 11 KV 5 WAY RMU (consisting of 2 Nos. LB s as Incomer, 3 Nos. 630A VCB s as Outgoings) on the existing plinth with rated voltage 12Kv, 630A, 21Ka/3sec, Outdoor type, extensible type on both sides, Internal arc 21KA for 1 Sec for Tank, floor mounted with internal copper bus bars, SF6 Insulated, completely Motorized, with modems and auto re-close & sectionalizes facility and with SCADA compatible Overload and earth fault protection Relay The unit shall have front cable entry (Suitable for termination of 1R x 3C x 95.120/150/185 Sq.mm Cable as per the switch gears and other items as enclosed at Annexure-A.
Make: ABB / SCHNIDER / SIEMENS / EATON; 3rd party inspection :- IRS, LLYODS, RITES, PDIL, EIL, MECON or any other authorized organization as approved by VPA
| 5 | No. |
| 2 | Supply, installation, testing & commissioning of 11 KV RMU 3-WAY RMU (consisting of 2 Nos LB s as Incomers, 2 No. 630A VCB s as Outgoing) on the existing plinth with rated voltage 12Kv, 630A, 21Ka/3sec, Outdoor type, extensible type on both sides, Internal arc 21KA for 1 Sec for Tank, floor mounted with internal copper bus bars, SF6 Insulated, completely Motorised, with modems and auto re-close & secationalizers facility and with SCADA compatible Overload and earth fault protection Relay The unit shall have front cable entry (Suitable for termination of 1R x 3C x 95.120/150/185 Sqmm Cable as per the switch gears and other items as enclosed at Annexure-A Make: ABB/SCHNIDER/SIEMENS/EATON; 3rd party inspection :- IRS, LLYODS, RITES, PDIL, EIL, MECON or any other authorized organization as approved by VPA | 1 | NO. |
| 3 | Supply and laying of 185 Sq.mm 3core,11 KV (E) HT cable, XLPE insulated and PVC sheathed, armored, aluminum conductor cable of approved brand as per IS 7090 part-II with all accessories as directed by Engineer in-charger including all material labour, tools and tackles and technical specification as enclosed at Annexure-B. Brand: Gloster / Polycab / RR Cable / KEI / Havells/NICCO; ; 3rd party inspection :- IRS, LLYODS, RITES, PDIL, EIL, MECON or any other authorized organization as approved by VPA | 5740 | Mtrs. |
| 4 | Supply and laying of 95 Sq.mm 3core,11 KV (E) HT cable, XLPE insulated and PVC sheathed, armored, aluminum conductor cable of approved brand as per IS 7090 part-II with all accessories as directed by Engineer in-charger including all material labour, tools and tackles and technical specification as enclosed at Annexure-B. Brand: Gloster / Polycab / RR Cable / KEI / Havells / NICCO; 3rd party inspection :- IRS, LLYODS, RITES, PDIL, EIL, MECON or any other authorized organization as approved by VPA | 1000 | Mtrs. |
| 5 | Compact Pre - Fabricated Packaged Sub -Station (as per IEC-60694/IS-3427) 11kV/433V consisting of 3 way SF6/VCB insulated compact RMU, oil cooled CRGO/Amoprhous Core Star - 2 Rated (5 -Star) Transformer and LT section with one MCCB / ACB as incoming and following outgoing MCCB feeders and with enclosure made of electronically galvanized steel sheet (min 2 mm Thickness) with powder coated finish, Copper bus-bar with LT Metering facility 1000 kVA Copper Wound Transformer, 1600 Amps ACB 50 kA 4 pole EDO type with microprocessor based protections for LT incomer and 1 Nos. 1200 Amps ACB 50 kA 4 pole EDO type with microprocessor based protections as outgoing feeder + 1 No. 250 Amps MCCB 4 pole 36 kA static based O/C and S/C protections Based for LT out going and technical specification as enclosed at Annexure-C. Brands:- Schneider / ABB / Siemens/ EATON/ L&K | 1 | Set |