| 3 | Salaries for Semi Skilled Technicians: - Wages to be paid for engaging semi-skilled technicians engaged for round the clock Operation and Maintenance of all firefighting equipment in UG Sump and only maintenance of Firefighting equipment as mentioned in below BOQ during 365 days (24 Hours X 7days). The scope also covers operation of pumps valves and also initial assistance in defect rectification subjected to firefighting equipment. The contarctor scope also includes the below mentioned works :-
(a) The rates shall include deputation of technicians in each shift including Technicians for reliver.The rates shall also include all the charges i.e., ESI, EPF, bonus, GST or any other miscellaneous charges which shall be paid from the contractor to the Technician.
(c) The contractor should provide required number of Technicians after visiting the site assessing the BOQ and scope of work with the below mentioned qualifications. The eligibility criteria of technicians will be verified by this department prior to recruiting by the contractor.
(d) The manpower must have single point of contact for regular communication and scheduling of maintenance.
(i) Mechanical Technician with SSC (Full Time) plus 02 years of ITI (Mechanical Trade through NCVT and experience of 03 Years as Pumps, valve operation and maintenance, Fire & safety drills and procedure.
(ii) Electrician with SSC (Full Time) Plus ITI (Electrician through NCVT) 02-year full-time course from Government recognized Institute with 05 years experience in Electrical Maintenance works in Industry/Hospitals after ITI. The electrician should possess electrical wiremen certification.
(e) The Bidder should provide 02 pairs of uniform Set ( Tshirt/Shirt & Trouser /Cargo Pant)with imprint of Fire Technician on back of the T-Shirt/Shirt and Company Logo on Front side of Pocket and Cargo Pant with multiple pockets . The bidder should provide 01 pair of safety shoes per each year. The charges for 02 No's uniform Set and safety shoes should be considered in the manpower charges only.
(f) The Contractor should Liase/Co ordinate , with Andhra pradesh State Disaster Response & Fire Service Dept. for Renewal of Occupancy NOC of all 09 No's Blocks in Hospital Campus so as to comply with the observations raised during surprise visit ,inspections and rounds .The processing fees for renewal of NOC will be paid by HBCH&RC,Visakhapatnam | 1.00 | Job |
| 4 | Fire Fighting System: This CAMC includes Diesel Engine Driven Pump, Electrcal driven pump, Jockey pump, Domestic water pumps, Terrace Booster pumps, Dewatering pumps, Air cushion tank, Valves, Sprinklers, Guages, Flow switches, Pressure switches, Strainers, External Hydrants, Hose reels, Internal and external Fire hose boxes, Hose pipes, Branch pipes, Siamese connections, Fire Brigade Breaching Inlets, Air Cushion tank. | | |
| 5 | CMC for Diesel driven Pump consisting of Pump and Diesel Engine ( 01 Set):- Including Maintenance of DG Set considering A-Check, B-Check & C- Check as recommended by the Engine Manufacturer , including all consumable and Non Consumable spares. Replacement of Batteries as and when required for staring of the engine , Repair /Replacment of Engine electronics, Safety switches , SMPS Switch.
Pump unit of Diesel Engine Driven Pump (Quantity - 01 No's) :- Centrifugal Horizontal split case fire fighting pump set having capacity of 2280 LPM at 88m head along with all accessories with Cl casing, standard fitting, bronze impeller, Stainless Steel shaft mechanical seal with water cooled heat exchanger diesel engine, having speed of 1500 rpm.CMC Including consumable and non consumable spares ,routine/scheduled maintenance cleaning of strainers, replacement of gaskets, vibration pads if required,alignment of engine with pump if required, Greasing at greasing points, replacement of seals and arrest any leaks from fittings and making operational for 24X7 operation in all respect Replacement of faulty pressure gauges Vibration Pads when required.Any other minor repairs in all respects to make the equipment operationally available 24X7 Maintenance of all associated pipelines for painting conosion Rubber Joint replacements, arresting of any type of leaks is also included.Note:- Major repairs in Pump has to be undertaken by authorised/OEM of the Pump.
PUMP MAKE KIRLOSKAR,PUMP TYPE DSM 100/36,CENTRIFUGAL PUMP, PUMP NO. 1723017352
QA NO. D10318A548/200 TOTAL HEAD-88M, DISCHARGE 136.800M3/HR,PUMP INPUT -44.459 KW,IMP DIA MM BR/365 SIZE & RPM 100 X 125 & 1500 MAT CODE 43,RECOMMENDED PRIME MOVER RATING -127 HP.
ENGINE Unit of Diesel Engine Driven Pump (Quantity - 01 No's) :- CMC Including consumable and non consumable spares ,routine/scheduled maintenance Supply of the charge of lubricants, fuel, distilled water for battery and other consumables related to Diesel Engine shall be included.CMC including Repair/Replacement of batteries, Strating Motor Dynamo, Air & Lub Oil Filters, replacement of rubber hose/bellows, Exhaust bellows, Silencer, Belts, Jubliee Clips.Any other minor repairs in all respects to make the equipment operationally available 24X7 Maintenance of all associated pipelines for painting, corrosion, Rubber Joint replacements, arresting of any type of leaks is also included. Note:- CMC to be undertaken by authorised/OEM of the Engine and Diesel for running the engine will be provided from HBCH&RC,Visakhapatnam
ENGINE TYPE 6R1080T,RATING KW/HP 93.47/127 HP,RPM 1500,RATING &STD ISO& 3046 thick
GOVERNNG CLASS M2, ENGINE NO.6H.2410.10/1720022,(DISEL SPRIEYR )BOSCH F0002 A0Z 421/PES6A95D320RS3559,BOSH SL NO. 75809688,BATTRIES MAKE EXIDE CARE BATTRIES QTY -02 NOS,ENGINE AIR CLEANER F6.504.01.0.00 | 1.00 | Job |