| 1 | Design, Supply, Installation, Integration, Testing and Commissioning with programming and configuration of Modbus RTU to Modbus TCP/IP gateway for Power Management System (PMS-SCADA based) on premise with Wired Architecture using Company LAN for 10,000 tags with Data base, Reporting tool and minimum 5 users webview provision at a time. PMS software should have Customized Dashboard Reporting with Historical database and Dedicated display of Energy and PQ Dashboard and PMS software shall be complete in all respect with following Functionalities.
1. Data Acquisition for metering devices, sensors, and other intelligent electric devices i.e., The PMS Software suitable for monitoring and control of Electrical Substations equipment s comprising of VCB panels (Breakers, relays), Transformers, S/S LT Panels and Sub Panels (Control of incomer breakers, status monitoring of all switchgears), Power Quality Equipment s. DG Synch, ATS, APFCR etc..
2. Power Quality analysis (including harmonics, voltage sags/swells, transients and voltage and current sinusoids), Power Quality compliance reporting for international standards (IEC61000 4 30)
3. Reports (100ms PQ Report, Energy Period over period Report, Energy usage by shift report, System configuration report, Hourly Usage Report, Data Export Report and any other customer requires) and Reports are easy to read and understand - they are fully customised reports with user-created templates
4. PMS software should be SCADA-based for device communication, integration, data acquisition, data management, monitoring & control and Business Intelligence with License engineering software.
5. PMS Software should be Customisable for SLD creation and SLD's are to be created for Overall Power Distribution and Individual Substation wise SLD of 6 No's i.e., can programme the system as per specific needs. The system has a customised SLD creation and Trends.
6. PMS Software should be Real-time reporting: Real-time communication for monitoring, control and diagnostics and system should supports multiple protocols and drivers like Modbus TCP/IP, Modbus RTU, IEC 61850, Simatic S7, OPC-UA, MQTT.
7. The system should provide a facility with alerts and acknowledgments.
8. PMS software should have Fully customized Dashboards to Create own dashboard to monitor KPIs such as:
Energy consumption
Power factor
Maximum demand
Regenerative power
Harmonic distortion
Specific energy consumption etc.
9. PMS software should have Compile energy monitoring for different loads to obtain holistic picture.
View instantaneous parameters like voltage, current and power factor at a single location, through aesthetic dial gauges.
Continuously monitor drive parameters, e g. power, energy, current, voltage, frequency etc.
10. Instant alerts by email & SMS notifications.
Make: L&T (L&K)/ Honeywell/ Schneider/ Siemens/Jhonson Control/Equivalent
| 1 | Lot |
| 4 | PC System
Supplying Installation Testing Commissioning of Client PC System comprising of PC Hardware with minimum 11th Gen Intel I7 processor CPU x64 (or better), compatible with 8 core processors minimum 3.1 Ghz and 32GB RAM, Hard Drive Space of 256 GB SSD and 2TB HDD and DVD ROM, Video card and monitor (24 inch full LED) capable of 1920 x 1080 pixel resolution or better with Ethernet adapter (10/100/1000 Mbps with RJ-45 connector), USB Ports (2Nos), NIC (2 No's - 4 ports) with 2 GB or higher Graphics card HDMI ports with USB keyboard, USB Mouse three button and scrolling, . With licensed Windows 10 Pro/11, 64 bits software or higher, MS Office 2013 or better 64 bits software, Anti Virus Software and Adobe reader as per suitable for BMS/PMS System complete etc. as required.
Make: Hewlett Packard/ Lenevo/ Dell
Monitor Make: Samsung/ Sony/LG/ Dell/HP | 1 | Each |
| 5 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Data Cable in existing conduit on surface/recessed including ties/ clamps, terminations etc., Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5 to +60 C, Bending Radius : < 4 X Cable Diameter at 5 C 1 C and Pulling Force : 11.5Kg etc. complete as required.
Make: D Link/AMP/Molex/Legrand/Krone/R & M . | 1400 | Meters |